Orb™ User Manual (Rev. 01a) 

DMX Primer 

 

 

 

The USITT DMX512-A data transmission protocol (DMX, from now on) is based on 
the EIA-485 standard and it has 512 channels (001 to 512). This system requires a 
controller (DMX controller), one or more DMX compatible fixtures, and a DMX circuit 
(also known as “DMX universe”) to link the fixtures to the controller. 
Depending  on  their  complexity  and  features,  DMX  compatible  fixtures  may  require 
from  one  to  more  than  30  DMX  channels  to  operate.  Some  DMX  fixtures  have 
multiple operation modes (also known as “personalities”), each with its own number 
of channels and controllable parameters. 

 

 

Starting Address 

 

 

 

In  the  DMX  system,  the  controller  sends  DMX  data  to  each  fixture  based  on  the 
fixture’s  starting  address.  The  starting  address  is  the  number  of  the  DMX  channel 
(001  to  512)  assigned  to  the 

fixture’s  first  control  channel  (Channel  1).  When 

assigning starting addresses to multiple fixtures, it is critical to ensure that no starting 
address  is  already  in  use  by  another  fixture  to  prevent  channels  from  overlapping. 
Otherwise, the affected fixtures may operate erratically. 

For instance, a user has two DMX compatible fixtures. 

Fixture “A” has four channels 

and 

fixture “B” has six channels. If the user configures the starting address of fixture 

“A” to “001”, channels 001 through 004 on the DMX controller will control fixture “A”. 
This means that the user should assign the starting address of 

fixture “B” to “005” or 

higher. For a starting ad

dress of “005”, the DMX controller would use channels 005 to 

010 to control fixture 

“B”.  

It is  possible  to  control multiple  fixtures  of the  same  type  by  assigning  each  one  of 
them the same starting address. In this case, all the fixtures would respond in unison 
(synchronized) to the signals from the DMX controller.

 

 

 

Fixture Linking (Daisy Chain) 

 

 

 

DMX  compatible  fixtures  receive  the  control  signals 
from  the  DMX  controller  through  the  DMX  cables. 
Each  fixture  has  a  DMX  In  and  a  DMX  Out 
connector.  The figure to the right illustrates how the 
fixtures link to each other using multiple segments of 
DMX  cable  in  a  sequential  format  called  “daisy 

chain”.  

The order in which the fixtures connect to the DMX 
controller  is  irrelevant  because  all  fixtures  receive 
the  same  DMX  signals  and  they  only  respond  to 
them  based  on  their  individual  starting  addresses. 
However,  it  is  important  to  notice  that  the 
connections  between  fixtures  should  always  be  as 
short and direct as possible.  

To ensure the integrity of the DMX signal, follow the 
recommendations of the EIA-485 standard: 

 

 

  The maximum recommended cable length is 500 m (1,640 feet). 

  The maximum recommended number of fixtures on the same daisy chain is 32. 

 

 

 

Connecting more than 32 fixtures on one daisy chain without the use of a DMX 
optically-isolated splitter may result in deterioration of the digital DMX signal. 

 
 

 

DMX 
Controller 

1

st

 DMX  

Fixture 

2

nd

 DMX  

Fixture 

To other  
fixtures 

Summary of Contents for ORB

Page 1: ...User Manual ...

Page 2: ...l Panel Operation 8 Configuration DMX 8 Starting Address 8 Configuration Standalone Modes 9 Sound Active Mode 9 Automatic Mode 9 Manual Mode 9 Master Slave Mode 10 DMX Channel Assignments and Values 10 5 Technical Information 11 General Maintenance 11 General Troubleshooting 12 Returns Procedure 13 Claims 13 Contact Information 13 DMX Primer 14 Starting Address 14 Fixture Linking Daisy Chain 14 DM...

Page 3: ...ettings A menu option not to be modified for example showing the operating mode current status Menu Settings A sequence of menu options to be followed ON A value to be entered or selected Icons Icon Meaning This paragraph contains critical installation configuration or operation information Failure to comply with this information may render the fixture partially or completely inoperative cause dam...

Page 4: ...h adequate ventilation at least 20 in 50 cm from adjacent surfaces Be sure that no ventilation slots on the unit s housing are blocked Always disconnect this product from the power source before cleaning it or replacing the fuse Make sure to replace the fuse with another of the same type and rating If mounting this product overhead always secure it to a fastening device using a safety cable The ma...

Page 5: ...Orb User Manual Rev 01a Page 5 of 17 2 INTRODUCTION Hanging bracket Bracket knob Fuseholder Power in Power out Microphone Microphone Adjustment DMX in Safety DIP switches DMX out ...

Page 6: ...ctrocution or fire Never connect this product to a rheostat variable resistor or dimmer circuit even if the rheostat or dimmer channel serves only as a 0 to 100 switch Power Linking This fixture provides power linking via the Edison IEC outlet located in the back of the unit Please see the diagram below for further explanation Power Linking Diagram You can power link up to 27 Orb units on 120 VAC ...

Page 7: ... appropriate weight capacity The bracket has a 13 mm hole which is appropriate for this purpose When mounting this product overhead always use a safety cable Before deciding on a location for this product always make sure that it will be easy to access the unit for maintenance and programming purposes When power linking multiple fixtures you must always consider the length of the power linking cab...

Page 8: ...tarting address that is too high you could restrict the access to some of the fixture s channels The Orb uses one DMX channel in DMX mode which defines the highest configurable address to 511 If you are not familiar with the DMX protocol you may refer to the DMX Primer section in the Technical Information chapter To select the starting address do the following 1 Set DIP 10 to the ON position 2 Usi...

Page 9: ...ixture that is operating in any standalone mode whether Static Automatic or Sound to a DMX string connected to a DMX controller This is because fixtures in standalone mode may transmit DMX signals that could interfere with the DMX signals from the controller To enable the Automatic Mode follow the instructions below 1 Set DIP switch 8 to the ON position Manual Mode To enable the Manual mode do the...

Page 10: ...ve unit to the DMX output of the master unit 4 Connect the DMX input of the subsequent slave units to the DMX output of the previous slave unit 5 Finish setting and connecting all the slave units Master unit 1 Set the master unit to operate in either Automatic or Sound mode as previously indicated 2 Make the master unit the first unit in the DMX daisy chain Configure all the slave units before con...

Page 11: ...aning frequency To clean this fixture follow the instructions below Unplug the fixture from power Wait until the fixture is cold Use a vacuum or dry compressed air and a soft brush to remove dust collected on the external surface vents Clean all external glass surfaces with a mild soap solution ammonia free glass cleaner or isopropyl alcohol Apply the solution directly to a soft lint free cotton c...

Page 12: ...the correct starting address on the fixture Use the right fader s on the controller Wrong polarity setting on the DMX controller Change the signal polarity on the controller Loose or damaged DMX cable Check the DMX cable before the faulty unit Internal problem Send product for repair Intermittent DMX Problems Signal cables are not DMX compatible Replace non DMX cables with true DMX cables Interfer...

Page 13: ...its own discretion to repair or replace returned product s Claims The carrier is responsible for any damage incurred during shipping to this product or any part that shipped with it Therefore if the received merchandise appears to have damages caused during shipping the customer must submit the damage report and any related claims with the carrier not CHAUVET The customer must submit the report up...

Page 14: ...ntrol fixture A This means that the user should assign the starting address of fixture B to 005 or higher For a starting address of 005 the DMX controller would use channels 005 to 010 to control fixture B It is possible to control multiple fixtures of the same type by assigning each one of them the same starting address In this case all the fixtures would respond in unison synchronized to the sig...

Page 15: ...n the other end The DMX protocol indicates that the XLR connectors must have five pins However most lighting fixtures use the 3 pin XLR connector The pin assignment of the 3 pin and 5 pin XLR connectors in a DMX cable is as follows Male Plug Female Plug Signal 3 Pin 5 Pin 5 Pin 3 Pin Signal Common 1 1 1 1 Common Data 2 2 2 2 Data Data 3 3 3 3 Data Not used 4 4 Not used Not used 5 5 Not used You ca...

Page 16: ...4 296 328 360 392 424 456 488 1 0 0 1 0 9 41 73 105 137 169 201 233 265 297 329 361 393 425 457 489 0 1 0 1 0 10 42 74 106 138 170 202 234 266 298 330 362 394 426 458 490 1 1 0 1 0 11 43 75 107 139 171 203 235 267 299 331 363 395 427 459 491 0 0 1 1 0 12 44 76 108 140 172 204 236 268 300 332 364 396 428 460 492 1 0 1 1 0 13 45 77 109 141 173 205 237 269 301 333 365 397 429 461 493 0 1 1 1 0 14 46 ...

Page 17: ...0 60 Hz Auto ranging Parameter 120 V 60 Hz 230 V 50 Hz Consumption 34 W 0 29 A 28 W 0 16 A Power I O Input Output Connectors IEC Edison IEC Cord plug Edison N A Light Source Type Power Lifespan LED 4 9 W 954 mA total 50 000 hours Color Power Red 1 3 W Green 2 W Blue 1 3 W Photo Optic Parameter Value Coverage angle 127º Thermal Maximum External Temp Cooling System 104 F 40 C Convection DMX I O Conn...

Reviews: