12
Bonding the cabinet to the telecommunications ground
GT-Series GlobalFrame Gen 2 Cabinets should be bonded to the telecommunications ground. The top
panel, side panels, doors and mounting rails on the GlobalFrame cabinet are electrically bonded to the
frame. A ground strap bonds the panels and doors to the frame. In order to bond the cabinet to the
telecommunications ground, use a One-Hole Ground Terminal Block (P/N 08009-001, ordered
separately) or one hole copper lug with ¼” (M6) or 3/8” (M8) hole to connect a bonding conductor to
the telecommunications ground or signal reference grid. Attach the block/lug to the cabinet frame
using a M6 bolt. Secure the lug to the center thread insert on the inside of the bottom front/rear
support on the cabinet.
P/N 08009-001
(ordered separately)