®
INSTALLATION INSTRUCTIONS
13
Warm air
Optional air ducts
can carry heat
to other rooms
Rear outlet of stove
Flexible tube
ø80mm
Air supply
Flue
Air supply duct must be fitted
to bring cool air into the stove.
This could be through an external
wall, from another room, or
from the same room as the stove.
PREPARATION OF FIREPLACE
If the fireplace contains combustible materials, inlet and outlet air
vents with an area of 246cm² each must be fitted below and above
the stove convection case to provide a continual air flow around the
stove. It is recommended that Calcium Silicate board is used
(130mm board, with a 100mm air gap between the stove and the
insulation (see Fig. 12).
If the fireplace does not contain combustible materials, it is still
recommended to have a layer of insulation or ventilate the space
between the casing and the outer wall. The insulation may consist of
a layer of mineral fibre or calcium silicate board. Insert this into the
opening before sliding in the convection casing.
Before fitting the appliance into an existing fireplace remove the
fireback and any loose in-fill material.
The surround and opening for the appliance must conform with
Fig.11. The flat area around the opening should be a minimum of
500mm wide and 600mm high. Ensure that the hearth and the base
in the opening are flat, level, and at right angles to the surround.
The air supply can be taken from using an external air kit or directly
from the convection casing. The air supply kit can be fitted in the
room or outside, in accordance with the requirements in 'Air Supply'
section (p11). The inlet grille must not constrict the airflow through
the duct and it must be permanently open. A semi rigid aluminium
flexible duct of no less than 80mm diameter is used to bring the air
to the stove . The duct must be less than 5.5m long, have no more
than five 90
º
bends and two 45
º
elbows. The 80mm diameter
spigot, provided with the stove should be fitted on the outside of the
convection case, using two self tapping screws and the duct should
be terminated on the spigot with a jubilee clip. The 100mm diameter
spigot provided should be fitted to the inside of the convection case
using two nuts on the outside and the self adhesive foam should be
glued into position around the circumference of the inside of the
80mm spigot in order to seal against the spigot on the back of the
stove when it is installed.
Fig. 13 Installation in standard chimney
Fig. 14 Air Supply
100mm air gap must be ventilated with inlet
and outlet apertures of minimum 246cm²
Top of stove
Non Combustible
Non Combustible
Calcium
silicate board
130mm
Fig. 12 Fireplace With Combustible Material
Flue
Flue collar
External air kit
to outside wall
Closure plate
A cover plate can be fitted to the rear outlet of the convection
casing. The outlet on the rear of the air box is to be left open
and no spigots are to be attached. This will provide external air
directly from the convection casing.