I-PR3I-01.doc 

 

 

Issue 03  

18/07/2019 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

                                                IOM 

 

PROTECTA - LED (IND)

 

 

 

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS  

Protecta – (LED) Luminaires (

Industrial). 

Important

Please read these instructions carefully before installing or maintaining this equipment. 
Good electrical practices should be followed at all times and this data should be used  
as a guide only. 

 

 
 
 
                              

MODEL SIZE 

DIMENSION ‘A’ 

DIMENSION ‘B’ 

02L 

742 

400 

04L 

742 

400 

07L 

1352 

700 

 

 

 

 
 
 
 
 
 
 
 

Summary of Contents for Protecta Series

Page 1: ... Protecta LED Luminaires Industrial Important Please read these instructions carefully before installing or maintaining this equipment Good electrical practices should be followed at all times and this data should be used as a guide only MODEL SIZE DIMENSION A DIMENSION B 02L 742 400 04L 742 400 07L 1352 700 ...

Page 2: ...e and condensation Any specific instructions concerning emergency Luminaires must be complied with Battery packs in storage should be cycled charged discharged charged every 9 months as per instructions below Always disconnect battery plug and socket for storage Any specific instructions concerning emergency luminaires must be complied with Warning Battery packs not cycled and stored for a year ma...

Page 3: ...and 6mm are available State which on order If work is to be done on any Luminaire which has already been connected to the electrical system it must be isolated from the system The diffuser cover is swung down and removed if convenient by swivelling back as far as possible and the reflector tray is then slid out after releasing the locking screws This gives access to the mains terminals Standard fi...

Page 4: ...5 Commissioning Energise the mains and check that LED s light when the supply is energised Emergency luminaires are supplied with the Battery plug Socket disconnected Just prior to switching power on connect battery plug and socket Emergency luminaires will require battery packs to be cycled to obtain the full duration capacity of the Ni Cd battery cells It is recommended that the unit is charged ...

Page 5: ...ge and replace if necessary 8 If it has been suspected that the Luminaire has suffered mechanical damage a stringent workshop check on all components should be made All components can be removed from the Luminaire for inspection 4 0 Electrical Fault Finding and Replacement The supply must be isolated before opening the Luminaire Any live fault finding must be done by a competent electrician and if...

Page 6: ...ry will remain on charge for an uninterrupted 24 hours At this time the module will conduct a commissioning test for the full duration The 24 hours recharge occurs also if a new battery is connected or the module exits the rest mode condition The following automatic commissioning duration test is only performed when a battery is replaced and fully charged after 24 hrs and the interval time is not ...

Page 7: ... test underway Slow flashing green 1 sec on 1 sec off Duration test underway Red LED on Load failure Open circuit Short circuit LED failure Slow flashing red 1 sec on 1 sec off Battery failure Battery failed the duration test or function test Battery is defect or deep discharged Incorrect battery voltage Fast flashing red 0 1 sec on 0 1 sec off Charging failure Incorrect charging current Green and...

Page 8: ...lektronischen Geräte Systeme 2011 65 EU RoHS II Directive On behalf of the Chalmit I declare that on the date the equipment accompanied by this declaration is placed on the market the equipment conforms to all technical and regulatory requirements of the above listed directives En tant que représentant du fabricant Chalmit je déclare qu à la date où les équipements accompagnant cette déclaration s...