Pag. 67 de 73
Manuale Didattico – ACO
Training manual :PIGMA Gal Evo
8 ERROR CODES
8.1
BOILER PROTECTION SYSTEMS.
There are two types of errors for malfunctions:
- Shutdown (solved by resetting);
- Safety stop (No Reset: the boiler will start working again properly when the cause is removed).
There is a third type of error code that is used to indicate a malfunction that does not stop the boiler which
continues to work properly (Indication).
8.1.1
Error codes
The error codes are divided in six different functional units, in other words the first figure indicates which
functional unit of the boiler is involved in the error:
Display
Description
Reset
PRIMARY CIRCUIT
1 01
Overheat
Reset
1 02
Heating proportional pressure short circuit or open circuit
No Reset
1 03
Circulation or presence of water: Gradient Tman > 7°C/sec for 3 times
Reset
1 04
Circulation or presence of water: Gradient Tman > 20°C/sec or Gradient Trit >
20°C/sec
Reset
1 05
Circulation or presence of water: Tman
– Trit> 55°C for 3 times
Reset
1 06
Circulation or presence of water: Trit > Tman + 10°C for 3 times
Reset
1 07
Circulation or presence of water: Trit > Tman + 30°C
Reset
1 08
Water missing on the primary circuit (P<Pmin) for boiler with minimum
pressure switch
on/off (par.247=1)
No Reset
1 10
Heating delivery probe open or short circuit (NTC1)
No Reset
1 11
Water missing on the primary circuit (P<Pmin) for boiler with pressure
sensor
(par. 247=2)
No Reset
1 12
Heating return probe open circuit or no signal (NTC2)
No Reset
1 14
Outdoor probe open circuit or no signal
No Reset
1 18
Primary Probes Test Fail
1 P1
Circulation or presence of water: Gradient Tman > 7°C/sec
Signalling
1 P2
Circulation or presence of water: Tman
– Trit> 55°C
Signalling
1 P3
Circulation or presence of water: Trit > Tman + 10°C
Signalling
SANITARY CIRCUIT
2 03
Tank probe open circuit or no signal
No Reset
2 05
Sanitary inlet probe open circuit (solar)
No Reset
2 09
Tank overheat
/
PCB
3 01
Eeprom display error
No Reset
3 02
GP
– GIU communication error
No Reset
3 03
PCB internal error
No Reset
3 04
More than 5 resets executed in 15 minutes
No Reset
3 05
PCB internal error
Reset
3 06 / 3 07
PCB card internal error
3 P9
Sched.Maintanace-Call Service
Reset
COMMUNICATION WITH PERIPHERALS
4.11
Room Sensor not available Z1
1
Primary circuit
2
Sanitary circuit
3
Electronic PCB
4
Communication with peripherals
5
Ignition and detection
6
Air inlet / Fume outlet
7
Zones