Heat pump water heater - OPERATING AND MAINTENANCE INSTRUCTIONS FOR THE USER
103
P1
TIME
Time setting
P2
T Max
Adjustment of the maximum obtainable temperature (from 65°C to 75°C).
A higher temperature value allows for using a greater amount of hot water.
P3
ANTI_B
Activation/deactivation of the Anti-Legionnaire’s Disease function (on/off). See
Paragraph 7.8
P4
TIME_
W
Maximum number of hours of daily heating (from 5h to 24h).
P5
HC-HP
Activation/deactivation of the two-tier rate operation mode. See Paragraph 7.10
P6
RESET
Resetting of all factory default settings.
P7
T Min
Adjustment of the minimum obtainable temperature (from 50°C to 40°C).
A lower temperature setting allows for more energy-efficient operation in the event of
limited hot water consumption.
P8
DEFRO
S
Activation/deactivation of the defrost mode (on/off).
If activated, this mode allows the heat pump to function at air temperatures as low as
-5°C.
7.8 Anti-legionnaire’s disease protection (function activated only through the installer menu)
If activated, the water heater automatically carries out the anti-legionnaire’s
disease protection function. The water is brought to a temperature of 65°C on a
monthly basis and for a maximum time of 15 minutes, so as to avoid germs from
developing in the water tank and piping (provided the water has not been
brought to T>57°C at least once for at least 15 minutes). The first heating cycle
is performed 3 days after the function has been activated. As these
temperatures may cause burns, it is advisable to use a thermostatic mixer.
During the cycle of antilegionella will be displayed “ANTI_B” alternately to the mode of operation, once the cycle is done
the set temperature remains the original one.
In the event that is enabled the two-tier rate signal HC-HP, the function will take place during the economic tariff. To
stop press "on/off".
7.9 Default settings
The appliance is manufactured with a series of default modes, functions or values, as indicated in the table below:
Parameter
Factory default setting
PRE-SET TEMPERATURE
52°C
P2
MAX. TEMPERATURE SETTABLE WITH THE HEATING
ELEMENT
65°C
P3
ANTI-LEGIONNAIRE’S DISEASE PROTECTION
DEACTIVATED
P4
TIME_W (no. of accepted hours of powering)
8h
P5
HC-HP (two-tier rate operation mode)
DEACTIVATED
P7
MINIMUM SETTABLE TEMPERATURE
50°C
P8
DEFROST (active defrost activation)
ACTIVATED
PROGRAM P1 TEMPERATURE PRESET
55°C
PROGRAM P1 TIME PRESET
06:00
PROGRAM P2 TEMPERATURE PRESET
55°C
PROGRAM P2 TIME PRESET
18:00