Page: 16/21 User Manual PULS-CTRL24, Rev.1-00: Software Utilities
FlashLoader 6 Firmware.txt -v
where
Firmware.txt
is the file containing the current firmware and
the number 6 indicates the port COM6 to which the device is con-
nected. The program should produce the following output:
Code file R:Final.txt from 11/04/2019, 12:00:00
Flash Loader 1.12
Verifying code file Final.txt
Verifying finished at Tue, 11/05/2019, 15:00:00
100495 (1888Fh) bytes processed, 99584 (18500h)
bytes verified
Resetting the target
Program finished ok
During the verify procedure, a message box is displayed at the device
display informing the user that the flash loader has been activated.
When the verify finishes without any error, the device is restarted.
!
Attention:
To be sure that the device cannot activate the attached
switches when the FlashLoader is active, disconnect the output cables
of the switches or remove these plugin modules from the chassis.
If any error occurs, do not proceed with the firmware upgrade. If you
cannot resolve the issues, contact the manufacturer. Note that even if
the verify fails and the flash loader at the device remains active, it is
safe to power the device off to restart it. However, a more safe and
comfortable alternative to that is to execute the following command:
FlashLoader 6 -i -f
This prevents the utility at the host computer from initializing the flash
loader utility at the microcontroller again and sends the reset com-
mand to the device.
If the verify has succeeded, you may start the firmware upgrade by
entering the command:
FlashLoader 6 Firmware.txt
where
Firmware.txt
is the file with the new firmware. The program
should produce the following output:
Code file R:Final.txt from 11/04/2019, 12:00:00
Flash Loader 1.12
Programming code file Final.txt
Programming finished at Tue, 11/05/2019, 15:00:00
CGC Instruments
Tel.: +49 (371) 355 098–55
Hübschmannstr. 18 | D–09112 Chemnitz
Fax: +49 (371) 355 098–60
internet: www.cgc-instruments.com