Never expose eyes or skin to UVC light from any source. Looking directly at the UVC

light may cause permanent eye damage or blindness. Never operate the CX-Pro Air Purifying System out
of the plenum. Avoid touching the glass portion of the lamp with your hands.

WARNING

SAFETY INSTRUCTIONS

Never expose eyes or skin to UVC light from any source. 

• Looking directly at the UVC light may cause permanent eye damage or blindness. 
•  Never operate the CX-Pro Air Purifier out of the plenum. 
• Designed for a closed duct system. Do not mount near a supply or a return air opening. 
•  All duct openings in direct line of site of the UVC light must be sealed with aluminum tape or

equivalent sealing methods. 

UVC light will break down plastic materials not rated for UV exposure, like wire

insulation, flex duct, drain pans, humidifiers, etc. 

•  The unit must be mounted at least 30" from the above stated types of materials. 
•  If it is necessary to mount the unit in direct line of sight of these types of materials, they must

be shielded with aluminum foil, aluminum foil tape, or sheet metal.

DO NOT mount this unit outdoors. 

•  This product is designed for indoor installation only (i.e. attics, crawl spaces, basements, etc.). 

Never touch broken lamp or internal contents of lamp. The lamp contains mercury. 

•  After opening the carton, unpack and inspect the unit and lamp for damage. Do not install

this unit if any damage is noticeable.  If lamp is damaged, cracked or broken, do not touch
lamp or other contents in carton. Close carton and return to seller immediately. 

• In case of accidental exposure to internal contents of lamp, wash hands and any other affected

skin area with mild detergent. Remove affected clothing immediately.  If skin surface is pierced,
seek medical attention immediately. 

NOTE:

If you touch the glass of the lamp, you should wipe the glass clean with isopropyl

alcohol and a lint free wipe. If the lamp is not cleaned, the film from hand oils will cause a
reduction in the light intensity.

Before installing or servicing a humidifier, air filter, HVAC system, or this unit,

etc., always turn all power OFF and have unit unplugged. Electrical shock can cause personal injury
or death. Never expose eyes or skin to direct UVC light from any source.

To prevent water damage or electric shock, do not mount unit under a humidifier.

This product is designed for indoor installation only (i.e. basements, crawl spaces,

attics, etc.). For use on gas fired, oil fired, electric and split system heat pump forced air systems

*

. This

product is NOT designed to be mounted outside on gas fired or heat pump packaged units

**

.

* Split system heat pumps are systems where the air handler and the air conditioning compressor are separate units. 
** Packaged units are systems where the air handler and the air conditioning compressor are built together and are installed

outside of the building. 

WARNING

WARNING

WARNING

WARNING

WARNING

WARNING

WARNING

Summary of Contents for CX-PRO

Page 1: ...Installation Maintenance CX PRO WHOLE HOUSE AIR PURIFIER READ AND SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE...

Page 2: ...t install this unit if any damage is noticeable If lamp is damaged cracked or broken do not touch lamp or other contents in carton Close carton and return to seller immediately In case of accidental e...

Page 3: ...Disconnect and lock out power supply before performing any installation work Working on or near energized equipment could result in death or serious injury Do not exceed voltage rating Severe damage t...

Page 4: ...direct exposure of plastic materials or air filters Use care to avoid damage to the AC coil wiring or other components while installing the CX Pro STEP 2 UVC LAMP BALLAST Unplug the unit before insta...

Page 5: ...ully back against the inside of the opening in the ductboard either from the sides or from top and bottom of the plate Finish the ductboard installation by sealing around the edges of the plate to the...

Page 6: ...ase of accidental breakage of glass 1 The lamp should be inspected and cleaned at least every 6 months Frequency depends upon the environment such as the type of air filter duration of use and replace...

Page 7: ...rmal compensating electronic ballast NOTE Wear oil free cotton gloves prior to procedure in case of accidental breakage of glass 1 Follow steps 1 4 in the Lamp Cleaning Procedure above After step 4 lo...

Page 8: ...are not covered by these warranty provisions All warranty claims must be processed through point of purchase All warranty repair work must be performed either at the factory or by a factory certified...