Page 25
Measurement of mate-
rial pile in the open air
– installation on hoist
frame
If it is non-adhesive medium, the extended connecting pipe can be soaked in the
medium for a long time (as long as the pipe is not corroded by the liquid and no im-
purities are attached to the inner wall of the pipe). In this way, the measurement
can be more accurate as it is not affected by other devices in the container.
The inner diameter of connecting pipe shall be as great as possible and the inclined
cut shall be smooth. The relationship between the height L and inner diameter φ of
connecting pipe is as shown below.
#
Length (L) of
Connecting
Pipe
Minimum Inner
Diameter (φ)
of Connecting
Pipe
Remarks
1
150mm
100mm
The inner wall of connecting pipe is free of
burr and bulges and vertical and the weld
joint shall be polished. The connection of
connecting pipe and tank top shall be
outwards polished at an oblique angle of
45º.
2
200mm
120mm
3
250mm
150mm
4
300mm
180mm
5
400mm
240mm