4.3 Solid Measurement
4.3.1 Flange Installation:
Similar to liquid medium measurement, the meter can be installed on the counter
flange of container connecting pipe. The solid reflecting surface is different from that
of the liquid and it is not a plane, which shall be considered during installation. The
probe emitting surface shall be perpendicular to the surface of solid to be measured
and the probe shall be exposed from the connecting pipe.
At the solid measurement site, in most cases, probe inside the connecting pipe will
lead to pulsating of measured data or “wave loss”.
To solve the problem, the universal flange can be used. In this case, the probe emit-
ting surface can easily be aligned to the reflecting surface of the solid to be measu-
red merely by rotating the flange.
Compact type sensor
installed on container
flange
Remote type sensor ins-
talled on container flan-
ge