CET s.r.l. Parallel Message Display
page 15
3.1.2. Using inputs in NEGATIVE logic
3.1.3. Input command timing
Generally, in order to be read, each device input should remain in stable conditions for at least 5 msec.
Coded commands that are stored at the positive variation (from 0 to 1) of the synchronism signal SY, should
respect the following minimum time conditions.
For fast VARIABLE updating from the PLC, we recommend using the following sequence type:
T1 T3 T2 T1
T3
T1 minimum: 1 millisecond
T2 minimum: 3 milliseconds
T3 minimum: 3 milliseconds
CODED
INPUTS
SY
9
A
B
D0
Dn
C NPN E
GND-EARTH
C = Collector E = Emitter
DISPLAY UNIT LOGIC UNIT
C NPN E
C NPN E
C NPN E
FIRST
VARIABLE
SECOND
VARIABLE
ETC.
CODED
INPUTS
SY
CODED
INPUTS
SY
5msec. 5msec. 5msec. 5msec.