What’s the meaning of the index lights on the panel?
BLP / BLY HEAT PUMP
english
The function of the LED on the panel is showing below:
Index Light
Name
Light
Flash
Temp Setting In the state of temp setting
-
Refrigeration
Refrigerating
Ready to refrigerate, in the state of compressor start delay
protection
Heat
Heating
Ready to heat, in the state of compressor start delay protection
Defrost
Defrosting
Ready to defrost, in the state of compressor start delay protection
Fan
Fan running
-
Alarm
-
Alarm state
The meaning of the LED display
The LED usually shows temperature, if it shows “SHr”, it means the temperature sensor is short, and “OPE” means the tempera-
ture sensor is open. The temperature and the alarm code (Axx) will show alternately when in the alarm state.
The code is showing below:
Code
Signification
Explanation
A11
External alarm
Alarm from external alarm signal, please refer to the internal parameter code “F50”
A21
Water temperature sensor error Open or short
(
showing “OPE” or “SHr”
)
A22
Outdoor machine sensor error Open or short
(
showing “OPE” or “SHr” when press the key “↓”
)
A99
Over probation time
If you have set the probation time F87, the alarm occurs when the accumulative running
time is over probation time, and the controller can not work.
17
Summary of Contents for HPP040
Page 2: ......
Page 11: ...BLP BLY HEAT PUMP english ATTENTION ...
Page 30: ...BOMBA DE CALOR BLP BLY español ATENCIÓN 29 ...
Page 49: ...47 POMPE Á CHALEUR BLP BLY français ATTENTION ...
Page 68: ...deutsch ACHTUNG 65 ...
Page 87: ...POMPA DI CALORE BLP BLY italiano ATTENZIONE 83 ...
Page 106: ...BLP BLY WARMTEPOMP nederlands OPGELET 101 ...
Page 125: ...BOMBA DE CALOR BLP BLY portugués ATENÇÁO 119 ...