8.3 Location of the Certification Label
Since the information given on the certification label affixed to the appliance always overrides
the information published, in any other media (owner’s manual, catalogues, flyers, magazines
and web sites) it is important to refer to it in order to have a safe and compliant installation. In
addition, important information about the stove can be found (model, serial number, etc.). The
certification label is located on the back of the stove.
It is recommended to note the stove serial number on page 5 of this manual since it will
be needed to precisely identify the version of the appliance in the event replacement parts or
technical assistance is required.
9. Clearances to Combustible Material
The clearances shown in this section have been determined by tests according to procedures
set out in safety standards ULC S627 (Canada), UL 1482 (U.S.A.) and UL 737 (U.S.A.). When
the stove is installed so that its surfaces are at or beyond the minimum clearances specified,
combustible surfaces will not overheat under normal and even abnormal operating conditions.
No part of the stove or flue pipe may be located closer to combustibles than the minimum
clearance figures given.
The clearances to combustible walls may be slightly different between Canada and the U.S.A.
and may also vary depending on the use of single or double wall flue pipe. The proper clearances
should be used depending on the stove location and type of flue pipe.
The clearances of the appliance and the flue pipes must be met individually, meaning the
appliance cannot be installed closer to the combustible materials than the single or double wall
pipe allows. For a safe way to reduce clearances refer to section