History
E8-1
Boiler status:
Boiler go to phases S7, C0 and OFF (it’s
appear after I8 notice and completion of adjusted retry
ignition number).
Possible causes:
Feeding tube temperature is higher than
80°C, interruption on el. connections between bimetal
sensor and boiler, connection to boiler, cold connection or
invalid bimetal sensor.
Pellet supply tube
temperature too high
E8-2
Boiler status:
Boiler go from phase S0 to OFF (it’s appear
after I8 notice and completion of adjusted retry ignition
number because of bimetal sensor information about too
high temperature in phase S0).
Possible causes
:
Feeding tube temperature is higher than
80°C, interruption on el. connections between bimetal
sensor and boiler, connection to boiler, cold connection or
invalid bimetal sensor.
Pellet supply tube
temperature too high
E9
Boiler status:
Boiler go to phases
S7, C0
and
OFF.
Possible causes
:
Interruption on el. connections between
sensor and boiler, connection to the boiler, cold connection
or invalid sensor.
Boiler sensor error
E10
Boiler status:
Boiler immediate go to phase
OFF
.
Possible causes
:
Key for power loading is not installed or
recognized, cold connection or invalid key.
Unknown boiler power
E11
Boiler status:
Boiler go to phase OFF after ending phase
S0 (retry start is allowed).
Possible cause
:
Invalid photocell
(
sending information
that flame exist in phase
S0)
.
Photocell error
E12
Boiler status:
Boiler immediate go to phase
OFF
.
Possible causes
:
Firebox resistance is too low in phases S2,
S3, S4, (S5). If any door or any opening for cleaning on boiler is
not properly closed, turbulators area is not closed or PVC tube
for pellet supply has holes. Interruption in el. connection
between safety pressure switch and boiler, connection to the
boiler, cold connection or invalid safety pressure switch.
Interruption or bad sealing of safety pressure switch pipe.
Safety pressure switch
E13
Boiler status:
Boiler immediate go to phase OFF.
Fan error
E14
Boiler status:
Boiler immediate go to phase OFF.
Memory error
E15
Boiler status:
Boiler immediate go to phase OFF.
Communication error with
motherboard
E16
Boiler status:
Boiler go to phases
S7, C0
and
OFF
.
Communication error with
sensor board
E18
Boiler status:
Boiler immediate go to phase OFF.
No flame in ignition phase
E19
Boiler status:
Boiler immediate go to phase OFF.
Flame disapeared
working phase
E20
Boiler status:
Boiler immediate go to phase OFF.
Flame disapeared 220V
Technical instructions REGULATION
PelTec / PelTec-lambda
47
E21
Boiler status:
Boiler immediate go to phase OFF.
Error grate cleaner
E17*
Only on
PelTec-lambda
Lambda probe error
a)
Error occurs in the phase of "OFF" The problem is with
el. heater which is integrated into the lambda probe
b) Error occurs in all phases except "OFF”
The problem is with the communication system within
the lambda(Cables, connectors, el. boards, software)