Temperature (configuration BUF)
2. TEMPERATURE (CONFIGURATION BUF)
2. Temperature
Diff.buf.tank temp.
3.
Buffer tank temp.
Min buf.tank temp.
1.
2.
default: 80°C
Minimum: 40°C
Maksimum: 85°C
The possibility of setting the desired temperature of the accumulation tank.
2.1 TEMPERATURE OF THE ACCUMULATION TANK
default: 20°C
Minimum: 5°C
Maksimum: 64°C
The possibility of setting the minimum temperature of the accumulation tank. When minimum
temperature of accumulation tank (upper sensor) is reached, all heat pumps connected to the boiler
control will be shut down. The minimum accumulation tank temperature does not affect the operation
of the DHW pump.
2.2 MINIMUM TEMPERATURE OF THE ACCUMULATION TANK
default: 10°C
Minimum: 5°C
Maksimum: 30°C
The possibility of setting the accumulation tank difference.
2.3 ACCUMULATION TANK DIFFERENCE
Possible selection:
Possible selection:
Possible selection:
Technical instructions REGULATION
PelTec / PelTec-lambda
17
Description of work:
The regulation reads on the upper sensor accumulation tank temperature, minimum accumulation
tank temperature and accumulation tank difference. At the bottom sensor, regulation reads the
accumulation tank shutdown difference that can be set in the installation menu (under PIN). When
the boiler is switched on, it works until the temperature on the lower sensor (T accumulation tank - T
accumulation tank shutdown difference) is reached. The boiler will turn ON again when
accumulation tank upper temperature (upper sensor) reach the (T accumulation tank - T
accumulation tank difference).