Centrometal CentroPelet ZVB 16 Technical Instructions Download Page 18

GB

Solution

Alarm signals

In the event of a working defect, the system informs the user about the type of failure occurred.
The following table summarises the alarms, kind of problem and possible solution:

Lower

Display

Upper

Display

Kind of failure

NO 

ACC

The 

boiler

 cannot start up

 

This is 

the first light-up

Fill in the tank with pellets

Start up again

NO 

FIRE

The pellet boiler 

boiler

 switched off while working

Fill in the tank with pellets

SONd 

FUMI

The  smokes  sensor  is  broken  or  not  connected 

to the pcb

Contact an Authorized Assistance Center

Contact an Authorized Assistance Center

HOT 

H20

The water temperature exceeds 90°C.

The circulating pump is blocked or there is no water 

in the hydraulic system

Check the power supply on the pump.

Check  limestone  does  not  block  the  pump  

impeller

SONd 

H20

The water sensor is not connected

There is a short circuit on the water sensor

Check the water sensor is connected

Contact an Authorized Assistance Center

ALAR

ALAR

ALAR

ALAR

ALAR

ALAR

COOL

ALAR

ALAR

ALAR

ALAR

SERV

HOT 

TEMP

The smokes temperature exceeds 280°C

Smokes sensor failure

Contact an Authorized Assistance Center

FAN

FAIL

dEP

FAIL

SIC 

FAIL

PRESS

Smokes extractor blocked or broken

Obstructed flue

Pellets tank overheating

The system pressure does not reach 0,5 bar or 

exceeds 2,3 bar

Contact an Authorized Assistance Center

Clean the flue or check there are no obstructed 

grids near the smokes exhaust

Re-set  the  safety  thermostat  for  pellets  on  the 

back  of  the 

boiler

.  If  the  problem  occurs  again, 

contact an Authorized Assistance Center

Reduce the system pressure

Charge the system

FIRE

There is no power supply

As  soon  as  the  power  supply  is  back,  the 

boiler

  starts  a  cooling  cycle.  After  completing 

the cycle it starts working automatically

The 

boiler

 has worked for 1300 

hours. Supplementary maintenance 

required

Regular checks should be carried out by the user, who should only contact the Authorized Assistance Center 
if no solution is found.

Summary of Contents for CentroPelet ZVB 16

Page 1: ...UE CentroPelet ZVB 16 20 24 32 TURZVB 01 2017 ENG Centrometal d o o Glavna 12 40306 Macinec Croatia tel 385 40 372 600 fax 385 40 372 611 TECHNICAL INSTRUCTIONS for installation use and maintenance of...

Page 2: ...an reach high temperatures Therefore pay attention and use the proper precautions above all in the presence of children elderly or disabled persons and animals Assembly must be performed by authorized...

Page 3: ...e every responsibility derived from improper use of the boiler from incorrect use by the user from un authorized modifications and or repairs from the use of replacement parts that are not original fo...

Page 4: ...upervision or instruction concerning use of the appliance Do not use the boiler as a ladder or scaffold Do not put clothes to dry on the boiler Any clothes hangers and suchlike must be kept a suitable...

Page 5: ...ammable maintain a minimum distance of 10 cm at the rear A di 40 cm at the side B and 150 cm at the front If the room contains objects which are believed to be particularly delicate such as drapes sof...

Page 6: ...ess steel pipe must not be used At the bottom of the flue pipe provide an inspection cap to allow periodic checking and cleaning which must be done annually Make a gas tight connection to the flue pip...

Page 7: ...must be a wind proof type and must be above the ridge Eventual structures or other obstacles that are higher than the chimney cap must not be too close to the chimney cap itself Fig 5 Characteristics...

Page 8: ...Water amount in stove Autonomy Power supply Power consume at nominal power Dimensions width depth height Net weight kW kg h mm Kg h W mm kg lit Model mm V Hz ZVB 16 4 29 14 4 1 02 3 37 89 11 87 87 80...

Page 9: ...t weight kW kg h mm Kg h W mm kg lit Model mm V Hz ZVB 20 5 21 17 51 1 2 3 88 92 13 88 82 80 50 65 50 54 16 5 230 50 100 300 610x785x1240 250 ZVB 24 Technical characteristics CentroPelet ZVB 20 24 80...

Page 10: ...in stove Autonomy Power supply Power consume at nominal power Dimensions width depth height Net weight kW kg h mm Kg h W mm kg lit Model mm V Hz ZVB 32 6 34 29 14 1 43 6 48 91 64 90 65 100 60 85 60 38...

Page 11: ...e LED is on when the parameter UT01 on the menu is not on OFF and the weekly or daily programming are set SET LED SYMBOL DESCRIPTION The LED starts up every time the boiler is loading pellets The LED...

Page 12: ...the water temperature press the key only once You will see the words Set H2o blinking on the upper display You will read the water temperature on the lower display To set the room temperature press th...

Page 13: ...ntrol panel for example 18 C and a sufficient shut down time has elapsed the boiler will come back on automatically and continue running until again reaching 20 C Regardless of the operation of the ex...

Page 14: ...ystem through the inlet pipe causing a phenomenon of oxygen that is highly damaging to life of the boiler To prevent this phenomenon it is possible to apply the following measures lower the speed of t...

Page 15: ...adjustment UT06 From 00 00 to 23 50 with 10 minute steps Boiler first shutdown time adjustment UT07 Between on off for days from 1 to 7 Week day selection first time activation UT08 From 00 00 to 23...

Page 16: ...day Day 6 Saturday Day 7 Sunday OFF Heating timer thermostat disabled UT07 Week day selection Press button o select the days of the week Press button to enable ON or disable OFF the pellet boiler boil...

Page 17: ...Other fuses to protect the electronic boards are to be found on the boards themselves Reduction motor if the motor stops the boiler continues to function until the flame goes out for lack of fuel and...

Page 18: ...or Check the water sensor is connected Contact an Authorized Assistance Center ALAR ALAR ALAR ALAR ALAR ALAR COOL ALAR ALAR ALAR ALAR SERV Hot temp The smokes temperature exceeds 280 C Smokes sensor f...

Page 19: ...of pellets in the tank or because the motor reducer for pellets loading got broken The boiler continues working until the pellets left in the brazier ends You will then read the words Alar No Fire on...

Page 20: ...idual combustion in the contact zone between the edges of the crucible and the support surface on the door crucible Parts Everyday Every 2 3 days Every week Every 15 days Every 30 days Every 60 90 day...

Page 21: ...Check every 60 90 days Cleaning the interior baffle smoke fan compartment Inside the compartment where there is the ash tray there is a second cover fixed by the cockerels which gives access to the co...

Page 22: ...s a fuse holding compartment which is located underneath the supply socket With a screwdriver open the cover of the fuse holding compartment and replace the fuse if necessary 3 15 AT delayed type Plug...

Page 23: ...lar Do not touch the boiler body and the various components do not approach the door it could cause burns Do not touch the exhaust fumes Do not perform any type of cleaning Do not dump the ashes Do no...

Page 24: ...other non original The operations marked in bold type must be carried out by specialised personnel Any kind of tampering or unauthorized substitution of non original of the boiler can be hazardous to...

Page 25: ...closed properly or gaskets worn 5 Boiler temperature is too high 6 Unsuitable pellets 7 Low pellet feed rate 8 Combustion chamber dirty 9 Smoke outlet obstructed 10 Smoke extraction motor failed 11 Pr...

Page 26: ...k the motor and capacitor and replace if necessary 3 Replace electronic board 4 Replace the control panel In the automatic position the boiler always runs at full power 1 Room thermostat set to maximu...

Page 27: ...of the boiler 1 It been set to a value of thermostat too high 2 It was set too much power to the implant 1 Lower the temperature in the boiler 2 Reduce the value of operating power The boiler goes in...

Page 28: ...2 fax 385 40 372 621 Centrometal d o o shall not be responsible for possible incorrect data caused by printing errors or error made in transcription and all figures and diagrams are for explanatory pu...

Reviews: