SURVEY OF SET POINTS
SETPOINT
MENU /
FUNCTION KEY
LOW
LIMITIN
G
VALUE
HIGH
LIMITIN
G
VALUE
PRESET
VALUE
OIL DIFF.PRESS CUT
SETP K/ F2
1,0 BAR
5,0 BAR
1.0 BAR
OIL DIFF.PRESS
ALARM
SETP K/ F3
1,5 BAR
5,0 BAR
2,0 BAR
FILTERDIFF CUTOUT
SETP K/ F4
0 BAR
2,5 BAR
2,3 BAR
FILTERDIFF ALARM
SETP K/ F5
0 BAR
2,5 BAR
1,8 BAR
VOLUME REG.FAKT
SETP L/ F2
0
100
25
T-SUCTION ALARM
SETP L/ F3
-60 °C
0 °C
-45 °C
T-DISCH. CUTOUT
SETP L/ F4
0 °C
150 °C
100 °C
T-DISCH ALARM
SETP L/ F5
0 °C
150 °C
90 °C
COMPRESSOR SIZE
SETP R/ F2
0
562
0
INJECTION YES/NO
SETP R/ F3
0=NO
1=YES
0=NO
OILPUMP TYPE
SETP R/ F4
0
2
0=PRELUBE
REFRIGERANT TYPE
SETP R/ F5
0
717
0
SLIDE VALVE MAX
SETP S/ F2
0
2500
1800
SLIDE VALVE MIN
SETP S/ F3
0
2500
250
SLIDE STOP MAX
SETP S/ F4
0
2500
1800
SLIDE STOP MIN
SETP S/ F5
0
2500
250
BOOSTER STOP
SETP T/ F2
0 BAR
10 BAR
4,5 BAR
BOOSTER START
SETP T/ F3
0 BAR
5 BAR
0,7 BAR
P-SUCTION SETP. 2
SETP T/ F4
-60 °C
60 °C
-10 °C
CAP MIN REG.FREE
SETP T/ F5
0 %
20 %
5 %
SLAVE START DELAY
SETP U/ F2
1 sec
900 sec
30 sec
SLAVE STOP
SETP U/ F3
25 %
95 %
70 %
STARTPRESSURE
SETP U/ F4
0 BAR
25 BAR
20 BAR
ECONOMIZER
SETP U/ F5
0=NO
1=YES
0=NO