5.5. FACTORY DEFAULT

In case of faulty functioning of ADA-4040A, like:

- no communication in the configuration mode,

- transmission errors on RS485/422 bus,

can be restored the factory default setting of the converter internal registers.

Factory default

Parameter

RS1 interface
RS485/RS422

RS2 interface
RS485/RS422

Converter address - Enable

unset

Converter address – Address

no active

Baud rate

9600bps

9600bps

Data bits

8

8

Parity

Non

Non

Stop bits

1

1

Interval between frames in bytes

4

4

Data flow control

DE-TOGGLE

DE-TOGGLE

Set SW1 microswitch mode as in the table below.

SW1-1

SW1-2

OFF

ON

Disconnect the power and after while connect again the power. After that, will be loaded the factory default setting to the converter 

internal registers.

After this operation, the converter parameters should be set again for operating in the application.

Set micro switch SW1 to run mode (Yellow LED will be OFF) as shown in the table below.

SW1-1

SW1-2

OFF

OFF

5.6. DIAGNOSTICS DATA TRANSMISSION

To readout diagnostics set SW1 to configuration mode (see pt OPERATION MODE).

Correctness of transmission proceed on RS1 and RS2 can be checked by readout the errors list by 

ADAConfig  

Software from the

converter   memory.   Frames   error   counter   will   be   increased,   in   case   of:   improper   speed   set   compared   to   real   speed   of   data

transmission. Parity error counter will be count the errors which can arise in case of misrepresent bytes in transmitted sign. This

counter will not work in case of disable control parity. For checking this counters press the button 

[Read transmission errors],

 and to

delete (zeroing of counters in the memory of the converter) press 

[Delete transmission errors].

In case of parity errors or frame errors check ADA-4040A converter's configuration and correctness connection of RS485 network to

RS1 port and addressable device to converter's RS2 port.

When diagnostic is finish, set SW1 micro-switch to run mode (see pt. OPERATION MODE).

6. OPERATION

The ADA-4040A converter can operate in to two modes: not addressable and addressable.

6.1. OPERATION IN NON ADDRESSABLE MODE

In this mode ADA-4040A operates as baud rate converter and data format converter and lets to set different baud rates and data

format on RS1 & RS2 interfaces. It lets connect to RS485 network old devices operate with non-configure baud rate and data format,

on which operate devices with different baud rate or data format.

6.2. OPERATION IN ADDRESSABLE MODE

In this mode ADA-4040A operates as baud rate converter and data format converter and lets to connect no addressable devices with

RSRS485/422 interface, transmitting data at different rates and formats of data frame to the RS485 bus, in the process of enabling the

cooperation with addressable devices.

Example connections of ADA-4040A are shown on figures below.

Frame of protocol for no addressable RS485/422 devices, connected to RS2 of ADA-4040A should be created in the following way:

ADDRESS ADA-4040A

FRAME OF NO ADDRESSABLE DEVICES

Where::

ADA-4040A ADDRESS 

- one byte of address from 1-255 scope,  - set in the memory of  ADA-4040A   
  during configuration in use of 

ADAConfig,

FRAME OF NO ADDRESSABLE DEVICES

- free sequence of bytes containing the appropriate frame of device, connected 
  to RS2 port. Not longer than 950 bytes.

11

ADA-4040A

Summary of Contents for ADA-4040A

Page 1: ...User manual ADA 4040A Addressable RS485 RS422 Baud Rate Converter 1 io_ada 4040a_v4 02_en ADA 4040A Copyright 2001 2017 CEL MAR sp j ...

Page 2: ...CTION 7 3 3 4 LINE TERMINATION 7 3 3 5 SLAVE DEVICE CONNECTION 7 3 4 CONNECTION OF POWER SUPPLY 7 4 ACTIVATION 8 4 1 SIGNALLING LEDS 8 4 2 TROUBLESHOOTING 8 5 CONFIGURATION 8 5 1 OPERATION MODE 8 5 2 CONFIGURATION BY THE USE OF ADACONFIG 8 5 2 1 CONFIGURATION OF ADDRESSING MODE 9 5 2 2 CONFIGURATION OF BAUD RATE AND DATA FORMAT 9 5 2 3 CONFIGURATION DATA FLOW CONTROL 9 5 3 FIRMWARE UPDATE 10 5 4 E...

Page 3: ...r supply circuit voltage Do not carry out the assembly or disassembly of the device if it is enabled This may result to short circuit and damage the device The device can not be used for applications that determine human life and health eg Medical 1 3 CE LABEL The CE symbol on the device CEL MAR means compatibility with electromagnetic compatibility Electromagnetic Compatibility Directive EMC 2014...

Page 4: ...on between next segments about the length up to 1200m The converter s galvanic separation protect system constructed on RS 485 RS 422 network and increase functioning reliability ADA 4040A supports an asynchronous baud rate up to 230 4 kbps through four or two pairs of twisted pair cables connected to screw terminals The converter use RX RX TX A TX B lines for functioning It is possible to connect...

Page 5: ...he cover then press bottom part to hear characteristic Click sound 3 2 COMPUTER CONNECTION To connect ADA 4040A converter via the RS1 port to computer equipped with RS 232 or USB interface is needed additional converter e g ADA I1040 RS232 to RS485 RS422 converter or ADA I9140 USB to RS485 RS422 converter or other which is connected to RS2 port of ADA 4040A The ways of connections of ADA 4040A to ...

Page 6: ...B GND Rx Rx RS2 screw connector RS485 RS422 ADA 4040A 5 GND GND 2 Rx 3 Tx RS232 connector DB 9F DCE Screw connector RS485 RS422 RS485 4W bus 9600Bd 8 O 1 RS232 connector DB 9M DTE PC or MASTER device ADA I1040 GND 5 Tx 2 Rx 3 Rt Rt Rx Rx Tx A Tx B RS485 2W Tx A Tx B GND Rx Rx Screw connector RS485 RS422 SLAVE 2400Bd 8 N 2 Tx A Tx B GND Rx Rx Screw connector RS485 RS422 SLAVE 19200 Bd 7 N 2 Tx A Tx...

Page 7: ...verter should be done by the use of DC power supplies regulated output voltage from 10 V to 30V min nominal power 2W e g ZS 12 250 or DR 15 24 Power cable from DC power supplies to device can not be longer than 3m Should be connected positive end of DC power supplies to Vss device terminal and negative end to Vss on terminal block ADA 4040A has protection against power supply reverse connection If...

Page 8: ...DA 4040A converter can operates in a few modes run configuration factory default emergency firmware update Those modes can be set by use SW1 located by terminal block RS2 after removing terminal cover marked as SW1 All available adjusting the SW1 switch are shown in table below Operation modes SW1 1 SW1 2 Mode OFF OFF Run ON OFF Configuration OFF ON Factory default Turning OFF and ON the power of ...

Page 9: ...data bites 5 6 7 8 control parity no control parity control control of none parity number of stop bits 1 2 frame spacing range from 4 to 255 silence time as frame s end 5 2 3 CONFIGURATION DATA FLOW CONTROL In the section Data flow control for RS1 RS2 interfaces can be set signal DE Off RS485 RS422 interface operates only in receiving data mode signal DE Toggle RS485 interface operates in receivin...

Page 10: ...confirmed by correct message Fig 8 Selection of firmware file During loading software the yellow LED located beside SW1 micro switch will blink showing data flow to ADA 4040A If the software loaded correctly yellow LED will be blink with frequency 1 Hz After that set micro switch SW1 to run mode as shown in the table below SW1 1 SW1 2 OFF OFF Yellow LED will be OFF 5 4 EMERGENCY FIRMWARE UPDATE In...

Page 11: ...e button Read transmission errors and to delete zeroing of counters in the memory of the converter press Delete transmission errors In case of parity errors or frame errors check ADA 4040A converter s configuration and correctness connection of RS485 network to RS1 port and addressable device to converter s RS2 port When diagnostic is finish set SW1 micro switch to run mode see pt OPERATION MODE 6...

Page 12: ...S 422 and RS 485 4 wire bus Additionally can be set data flow control for RS1 RS485 RS422 interface and RS2 RS485 RS422 interface according to pt CONFIGURATION BY THE USE OF ADACONFIG Figures below present possibility of using the addressable ADA 4040A baud rate converter Fig 9 Connection of no addressable RS422 devices to RS485 bus Fig 10 Connection of RS485 bus segments with different baud rate ...

Page 13: ...r without inlets plug in screw terminal block 3 9 SPECIFICATION TECHNICAL DATA Transition Parameters Interface RS 485 RS 422 RS1 RS 485 RS 422 RS2 Connector Screw terminal block max Ø 2 5mm2 Screw terminal block max Ø 2 5mm2 Line length 1200 m depend on baud rate 1200 m depend on baud rate Max number of connected device 32 Baud rates 300 600 1200 1800 2400 4800 7200 9600 14400 19200 28800 38400 57...

Page 14: ... to the PN EN60950 norm Environment Commercial and light industrial Environmental Parameters Operating temperature 30 60 C Humidity 5 95 non condensing Storage temperature 40 70 C Casing Dimensions 53 x 90 x 62 mm Material Noryl UL 94 V O Degree of casing protection IP40 Degree of terminal protection IP20 Weight 0 10 kg According to standards DIN EN50022 DIN EN43880 Location during work Free Mount...

Page 15: ...15 ADA 4040A ...

Page 16: ... transmission converters with interface RS232 RS485 RS422 USB Ethernet Wi Fi Current Loop Fibre Optic Converters and other Please contact us to tell how you like our products and how we can satisfy you present and future expectation CEL MAR sp j Computers Science and Electronic Factory str Sciegiennego 219C 25 116 Kielce POLAND Tel 48 41 362 12 46 Tel fax 48 41 361 07 70 Web http www cel mar pl Of...

Reviews: