Function 0x03 / 0x04 are used for readout of the value from measuring channel (sensor).
The value from measuring channel (sensor) is presented by a 16-bit register.
The registers with measuring value of lighting are in the format of 16-bit signed integer (C/C++ type short int).
The actual value of lighting in percent % (0 – 100 [%Lux]) is obtained from readout register according to algorithm from paragraph
7.3.1.1 by use appropriate factor value
DW=10
(table p.7.3.1.1).
7.3.1.5. FUNCTION 0x03 / 0x04 – READOUT OF SUNLIGHT FROM MEASURING CHANNEL [4X
/ 3X-REFERENCES]
Function 0x03 / 0x04 are used for readout of the value from measuring channel (sensor).
The value from measuring channel (sensor) is presented by a 16-bit register.
The registers with measuring value of sunlight are in the format of 16-bit signed integer (C/C++ type short int).
The actual value of sunlight in percent % (0 – 100 [%SLux]) is obtained from readout register according to algorithm from paragraph
7.3.1.1 by use appropriate factor value
DW=100
(table p.7.3.1.1).
7.3.1.6. FUNCTION 0x03 / 0X04 – READOUT OF TEMPERATURE SET IN TEMPERATURE
ADJUSTER FROM MEASURING CHANNEL [4X / 3X-REFERENCES]
Function 0x03 / 0x04 are used for readout of the value from measuring channel (sensor).
The value from measuring channel (sensor) is presented by a 16-bit register.
The registers with value of temperature set by the adjuster are in the format of 16-bit signed integer (C/C++ type short int).
The actual value of temperature set by the use of temperature adjuster in °C (5 – 40 [TA(°C)]) is obtained from readout register
according to algorithm from paragraph 7.3.1.1 by use appropriate factor value
DW=10
(table p.7.3.1.1).
7.3.1.7. FUNCTION 0x03 / 0X04 – READOUT OF PERCENTAGE VALUE SET IN PERCENT
ADJUSTER FROM MEASURING CHANNEL [4X / 3X-REFERENCES]
Function 0x03 / 0x04 are used for readout of the value from measuring channel (sensor).
The value from measuring channel (sensor) is presented by a 16-bit register.
The registers with percent value set by the adjuster are in the format of 16-bit signed integer (C/C++ type short int).
The actual value set in percent adjuster in percent % (0 – 100 [PA(%)]) is obtained from readout register according to algorithm from
paragraph 7.3.1.1 by use appropriate factor value
DW=10
(table p.7.3.1.1).
7.3.1.8. FUNCTION 0x03 / 0x04 – READOUT OF CO2 CONCENTRATION MEASURING
CHANNEL [4X / 3X-REFERENCES]
Function 0x03 / 0x04 are used for readout of the value from measuring channel (sensor).
The value from measuring channel (sensor) is presented by a 16-bit register.
The registers with measuring value of CO2 concentration are in the format of 16-bit signed integer (C/C++ type short int).
The actual value of CO2 concentration in ppm (350 – 10000 [ppm]) is obtained from readout register according to algorithm from
paragraph 7.3.1.1 by use appropriate factor value
DW=1
(table p.7.3.1.1).
7.3.1.9. FUNCTION 0x03 / 0x04 – READOUT OF TEMPERATURE VALUE OF SENSOR PT100 ,
PT500, PT1000 FROM MEASURING CHANNEL [4X / 3X-REFERENCES]
Function 0x03 / 0x04 are used for readout of the measurement value from measuring channel (DES-216-PT transducer).
The measurement value from measuring channel (DES-216-PT transducer) is presented by a 16-bit register.
The registers with measurement value of temperature from transducer PT100, PT500, PT1000 are in the format of 16-bit signed
integer (C/C++ type short int).
The actual value of measurement value of temperature from DES-216-PT transducer in °C (-200 – +600 [°C PT100] is obtained from
readout register according to algorithm from paragraph 7.3.1.1 by use appropriate factor value
DW=10
(table p.7.3.1.1).
7.3.1.10. FUNCTION 0x03 / 0x04 – READOUT OF VOLTAGE VALUES 0-10V DC FROM
MEASURING CHANNEL [4X / 3X-REFERENCES]
Function 0x03 / 0x04 are used for readout of the measurement value from measuring channel (DES-216-U transducer).
The measurement value from measuring channel (DES-216-U transducer) is presented by a 16-bit register.
The registers with measurement voltage values from DES-216-U transducer, are in the format of 16-bit signed integer (C/C++ type
short int).
The actual value of measurement value of voltage from DES-216-U transducer in VDC (0 – 10 [V U10] is obtained from readout
register according to algorithm from paragraph 7.3.1.1 by use appropriate factor value
DW=100
(table p.7.3.1.1).
7.3.1.11. FUNCTION 0x03 / 0x04 – READOUT OF AMPERAGE VALUES 0-20mA DC FROM
MEASURING CHANNEL [4X / 3X-REFERENCES]
Function 0x03 / 0x04 are used for readout of the measurement value from measuring channel (DES-216-I transducer).
The measurement value from measuring channel (DES-216-I transducer) is presented by a 16-bit register.
The registers with measurement amperage values from DES-216-I transducer, are in the format of 16-bit signed integer (C/C++ type
short int).