If before readout the configuration of measure channels, were not connected temperature sensors to the module, the list of the column
[U.m.]
will be empty. In this case, connect sensor (s) to ADA-401WP and again readout the configuration of measurement channels
from ADA-401WP memory, by pressing [
Read Configuration form Module]
.
Adding next sensors, consist in connecting them to the module and readout the configuration of measurement channels from ADA-
401WP memory, by pressing [
Read Configuration form Module]
.
ATANTION!!
If wish to new added sensors were assigned to further measurement channels, should set
Assigned
for before added sensors, and
save the channel configuration to the module by pressing
[Save Configuration to Module].
After adding all sensors to the measurement channels, should be set an order of sensors and make the configuration of
measurements channels as described below.
5.3.2. CHANGING SENSORS ORDER
The order of sensors can be changed by:
- sensor displacement,
- sensors exchange,
- AAS procedure.
All above method are described below.
5.3.2.1. SENSOR DISPLACEMENT
To displacement the sensor from one channel to the other, under button
Move Sensor from Channel to Channel,
enter to field
from
the number of channel from which the sensor will be moved and to field
to
enter the number of channel to which the sensor will be
moved. Press the button
Move Sensor from Channel to Channel.
Save the configuration to module memory by pressing button
Save Configuration to Module.
To the module memory will be saved only configuration of measuring channels which fields were marked in ping.
5.3.2.2. SENSORS EXCHANGE
To exchange the sensors enter to the fields
from
and
on
the channel number to which will be exchange the sensors and press the
button
Exchange Sensors from Channel on Channel
. Save the configuration to module memory by pressing button
Save
Configuration to Module
.
To the module memory will be saved only configuration of measuring channels which fields were marked in ping.
5.3.2.3. CHANGING TEMPERATURE SENSORS ORDER BY THE USE OF AAS PROCEDURE
If the location of sensors in the installation is unknown, can be added to measurement channel by using
Automatic Assign Sensor
function.
The procedure of Automatic Assign Sensor (AAS) is made in the following steps:
1.Connect 1-WIRE sensors bus to ADA-401WP.
2.Select (in the ADAUtil software) branch
Configuration => Communication =>ADA-401WP
on left panel and on right press
Read
Configuration form Module.
3.In section
Automatic Assign Temperature Sensor to Measure Channel
select option
Enable Automatic Assign Temperature
Sensor to Measure Channel,
then in edition field
Temperature AAS,
enter the upper temperature limit beyond which it will
automatically assign a heated sensor to the measurement channel. The sensors are assigned sequentially to the channel number
0, 1, 2, 3 … e.t.c.
4.Press button
Save configuration to module
.
5.Select branch
Configuration => Communication =>
ADA-401WP => Measure Channels
on left panel and on right
press
Read
Configuration form Module
.
6.After readout the configuration press
Sensors Monitoring.
7.Then heat sensors in the selected order (e.g. as fig. below) and if sensor temperature exceeds the setted temperature AAS,
sensor will be automatically assign for measuring channel. Any assignment of a sensor for measuring channel is indicated by the
module and program of short tone/Beep.
8.This procedure is ended by pressing again the button
Sensors Monitoring
.
9.Select branch
Configuration => Communication =>
ADA-401WP
, then in section
Automatic Assign Temperature Sensor to
Measure Channel,
disable the option
Enable Automatic Assign Temperature Sensor to Measure Channel
.
10. Press button
Save Configuration to Module
. It will disable the algorithm of
Automatic Assign Sensor to Measuring Channel
in ADA-401WP module.
13