CEL-MAR ADA-401WP User Manual Download Page 13

If before readout the configuration of measure channels, were not connected temperature sensors to the module, the list of the column

[U.m.]

 will be empty. In this case, connect sensor (s) to ADA-401WP and again readout the configuration of measurement channels

from ADA-401WP memory, by pressing [

Read Configuration form Module]

.

Adding next sensors, consist in connecting them to the module and readout the configuration of measurement channels from ADA-
401WP memory, by pressing [

Read Configuration form Module]

.

ATANTION!!

If wish to new added sensors were assigned to further measurement channels, should set 

Assigned 

for before added sensors, and

save the channel configuration to the module by pressing 

[Save Configuration to Module].

After   adding   all   sensors   to   the   measurement   channels,   should   be   set   an   order   of   sensors   and   make   the   configuration   of

measurements channels as described below.

5.3.2. CHANGING SENSORS ORDER 

The order of sensors can be changed by:

- sensor displacement,

- sensors exchange,

- AAS procedure.

All above method are described below.

5.3.2.1. SENSOR DISPLACEMENT

To displacement the sensor from one channel to the other, under button 

Move Sensor from Channel to Channel,

 enter to field 

from

the number of channel from which the sensor will be moved and to field 

to 

enter the number of channel to which the sensor will be

moved. Press the button 

Move Sensor from Channel to Channel. 

Save the configuration to module memory by pressing button 

Save Configuration to Module.

To the module memory will be saved only configuration of measuring channels which fields were marked in ping.

5.3.2.2. SENSORS EXCHANGE

To exchange the sensors enter to the fields 

from

 and 

on

 the channel number to which will be exchange the sensors and press the

button  

Exchange   Sensors   from   Channel   on   Channel

.  Save   the   configuration   to   module   memory   by   pressing   button 

Save

Configuration to Module

.

To the module memory will be saved only configuration of measuring channels which fields were marked in ping.

5.3.2.3. CHANGING TEMPERATURE SENSORS ORDER BY THE USE OF AAS PROCEDURE

If the location of sensors in the installation is unknown, can be added to measurement channel by using 

Automatic Assign Sensor

function.

The procedure of Automatic Assign Sensor (AAS) is made in the following steps: 

1.Connect 1-WIRE sensors bus to ADA-401WP.
2.Select (in the ADAUtil software) branch 

Configuration => Communication =>ADA-401WP

 on left panel and on right press 

Read

Configuration form Module.

3.In section 

Automatic Assign Temperature Sensor to Measure Channel 

select option

 Enable Automatic Assign Temperature

Sensor to Measure Channel,

 

then in edition field  

Temperature AAS,

 

enter  the upper temperature limit beyond which it will

automatically assign a heated sensor to the measurement channel. The sensors are assigned sequentially to the channel number

0, 1, 2, 3 … e.t.c.

4.Press button

 Save configuration to module

.

5.Select branch

 

Configuration => Communication =>

ADA-401WP => Measure Channels

 

on left panel and on right

 

press 

Read

Configuration form Module

.

6.After readout the configuration press 

Sensors Monitoring.

7.Then heat sensors in the selected order (e.g. as fig. below) and if sensor temperature exceeds the setted temperature AAS,

sensor will be automatically assign for measuring channel. Any assignment of a sensor for measuring channel is indicated by the

module and program of short tone/Beep.

8.This procedure is ended by pressing again the button 

Sensors Monitoring

.

9.Select branch

 

Configuration => Communication =>

ADA-401WP

, then in section 

Automatic Assign Temperature Sensor to

Measure Channel, 

disable the option

 Enable Automatic Assign Temperature Sensor to Measure Channel

.

10. Press button

 Save Configuration to Module

. It will disable the algorithm of 

Automatic Assign Sensor to Measuring Channel

in ADA-401WP module.

13

ADA-401WP

Summary of Contents for ADA-401WP

Page 1: ...User manual ADA 401WP 1 WIRE to MODBUS RTU Measuring Module 1 io_ada 401wp_v 1 24_en ADA 401WP Copyright 2001 2017 CEL MAR sp j...

Page 2: ...1 SENSOR DISPLACEMENT 13 5 3 2 2 SENSORS EXCHANGE 13 5 3 2 3 CHANGING TEMPERATURE SENSORS ORDER BY THE USE OF AAS PROCEDURE 13 5 3 3 SENSORS REMOVING 14 5 3 4 MEASUREMENT CHANNEL PARAMETERS CONFIGURAT...

Page 3: ...MEASURING CHANNEL 4X 3X REFERENCES 24 7 3 1 8 FUNCTION 0x03 0x04 READOUT OF CO2 CONCENTRATION MEASURING CHANNEL 4X 3X REFERENCES 24 7 3 1 9 FUNCTION 0x03 0x04 READOUT OF TEMPERATURE VALUE OF SENSOR PT...

Page 4: ...ly of the device if it is enabled This may result to short circuit and damage the device The device can not be used for applications that determine human life and health eg Medical 1 3 CE LABEL The CE...

Page 5: ...485 line is made on the basis of 600W protectors diodes and fuses To RS485 Bus can be connected 32 devices ADA 401WP Additional converter like ADA I1040 RS232 to RS485 or ADA I9140 USB to RS485 enabl...

Page 6: ...erter from power circuit device that generates large impulse interference such as transmitters contactors 3 1 ASSEMBLING ADA 401WP enclosure is adapted to assembly on TS 35 DIN35 rail To install shoul...

Page 7: ...Bd Should be used Line Termination resistor if the distance is over 1000m 9600Bd or 700m 19200Bd transmission Example connection of Rt connected to screw terminal block of RS485 422 interface are show...

Page 8: ...500 However when building the network remember that each sensor is a shortening of 0 5 meters and 100 meters of cable causes additional capacity load data line 5nF increasing signal distortion The rea...

Page 9: ...ecking RS485 interface Diagnosis 1 WIRE interface Diagnostic System Diagnostic Measurement channels Diagnostic 5 CONFIGURATION Configuration of ADA 401WP module should be made by the use of ADAUtil so...

Page 10: ...disable disable manufacturer setting Errors that are signalled by short sound errors of sensors searching errors of reading temperature from sensors errors in RS485 communication errors of CRC sensor...

Page 11: ...ingle reading sensors and Enable write TL and TH registers for DS18xxx are available from 2 005 firmware version and 1 7 1 0 version of ADAUtil 5 2 5 AUTOMATIC ASSIGN SENSORS TO MEASUREMENT CHANNELS A...

Page 12: ...the table below Table indications of sensors Sensor Unit of measurement Sensor Unit of measurement Temperature C voltage converter 0 10V DC V U10 Relative humidity RH current converter 0 2mA DC mA A2...

Page 13: ...iguration to module memory by pressing button Save Configuration to Module To the module memory will be saved only configuration of measuring channels which fields were marked in ping 5 3 2 3 CHANGING...

Page 14: ...hPa to 12 70hPa for digital atmospheric pressure sensors DES 216 AP DES 300 AP etc Enable activation this field will cues actualisation of measurement and status for channel deactivation will cues blo...

Page 15: ...in loaded file can be changed the module software Process of software update is visualized by ADAUtil in use of Progress Window and after proper update confirmed by correct message Fig 11 Choice of s...

Page 16: ...mode value visualization of temperature measurement with the 0 5 C accuracy transmission errors on the 1 WIRE bus restore factory default and reset register Set the SW1 microswitch as in the table bel...

Page 17: ...ter counter of Button the number of RST Reset button Register counter of Brown On specifies the number of the operating voltage drops below allowable voltage level After that can be set the switch sec...

Page 18: ...ble below SW1 1 SW1 2 OFF OFF Yellow LED will be OFF 6 3 DIAGNOSTIC OF MODBUS PROTOCOL After finishing diagnostic of measurement channels of each ADA 401WP module in installation can be started diagno...

Page 19: ...ters of channels 6 3 1 CONFIGURATION OF MODBUS RTU COMMUNICATION MODBUS Monitoring window has options for configuration of MODBUS RTU communication Module Address 1 247 enter the address of ADA 401WP...

Page 20: ...sation of measurement and status for channel deactivation will cues block actualisation Assigned activation this field will cues adding a sensor to the Channel Deactivation will cues that in case of n...

Page 21: ...condition R 16 bit register 30202 40202 1 201 Channel condition R 16 bit register 30203 40203 2 202 Channel condition R 16 bit register 30204 40204 3 203 Channel condition R 16 bit register 30204 4020...

Page 22: ...re C 100 PT1000 sensor s temperature C PT1000 10 Relative humidity RH 10 0 10VDC transducer V U10 100 Lighting natural or unnatural Lux 10 0 20mADC transducer mA A20 100 Sunlight SLux 10 Circuit DS240...

Page 23: ...during inquiry converting 03 CRC Lo 1 byte 04 CRC Hi 1 byte 7 3 1 2 FUNCTION 0x03 0x04 READOUT OF RELATIVE HUMIDITY FROM MEASURING CHANNEL 4X 3X REFERENCES Function 0x03 0x04 are used for readout of...

Page 24: ...CTION 0x03 0x04 READOUT OF CO2 CONCENTRATION MEASURING CHANNEL 4X 3X REFERENCES Function 0x03 0x04 are used for readout of the value from measuring channel sensor The value from measuring channel sens...

Page 25: ...erial number 40 0 402 Byte 4 of serial number 01 Bajt 5 of serial number 00 0 403 Byte 6 of serial number 00 Bajt 7 of serial number 23 Query of circuit serial number from channel nr 0 Byte no Designa...

Page 26: ...status Byte Hi from ver 1 008 firmware 0 Sensor in processing 0 No 1 Yes 0 Short circuit on the 1 Wire bus 0 No 1 Yes 1 Sensor detected 0 No 1 Yes 1 DS18xx circuit present on 1 WIRE bus 0 0 No 1 Yes 2...

Page 27: ...1 byte 83 84 02 Error code 1 byte 01 unknown function 02 unknown data address 03 unknown data value 04 unknown error while inquiry converting 03 CRC Lo 1 byte 04 CRC Hi 1 byte 8 SPECIFICATION TECHNICA...

Page 28: ...ng Degree of casing protection IP40 Degree of terminal protection IP20 Weight 0 10 kg According to standard DIN EN50022 DIN EN43880 Location during work Free Mounting method On the rail compliant with...