Query of register Eac
Byte no
Designation
Size
Value [hex]
00
Inverter address
1 byte
11 [ 11 to F7]
01
Function code
1 byte
03 / 04
02
Registry address Hi
1 byte
00
03
Registry address Lo
1 byte
08
04
Registry number Hi
1 byte
00
05
Registry number Lo
1 byte
02
06
CRC-Lo
1 byte
---
07
CRC-Hi
1 byte
---
Example.
Query of AC network energy meter
Eac
from registry address 40009 / address 30009
11-03-00-08-00-02-CRCLo-CRCHi
11-04-00-08-00-02-CRCLo-CRCHi
Response with register value
Eac
Byte no
Designation
Size
Value [hex]
00
Inverter address
1-byte
11 [ 11 to F7]
01
Function code
1-byte
03 / 04
02
Number of data bytes N-byte
04
03
Dane1-Hi
1-byte
00
04
Dane1-Lo
1-byte
00
05
Dane2-Hi
1-byte
0B
06
Dane2-Lo
1-byte
90
07
CRC-Lo
1-byte
---
08
CRC-Hi
1-byte
---
Example.
Readout of AC network energy meter
Eac
from registry address 40009 / address 30009
11-03-04-00-00-0B-90-CRCLo-CRCHi
11-04-04-00-00-0B-90-CRCLo-CRCHi
In respond the value of AC network energy meter
Eac
is presented as 4-byte with values:
Eac
= 0x00000B90 => 2960/100 => 29,60 kWh
Response - in case of error
Byte no
Designation
Size
Value [hex]
00
Inverter address
1-byte
11 [ 11 do F7]
01
Function code
1-byte
83 / 84
02
Error code
1-byte
01 - unknown function
02 - unknown data address
03 - unknown data value
04 - SunMaster inverter not respond or is faulty
03
CRC-Lo
1-byte
04
CRC-Hi
1-byte
8.3.1.3. READOUT OF SOLAR PANEL VOLTAGE VALUE Usol FROM INVERTER [4X / 3X-
REFERENCES]
The measurement value of solar panel voltage, readout from 16-bit register
Usol
MODBUS-RTU (see p.8.1.) is presented in the
format integer 16-bit with sign (in C/C++ type short int).
Query of solar panel voltage
Usol
from registry address 40003 / address 30003
11-03-00-02-00-01-CRCLo-CRCHi
11-04-00-02-00-01-CRCLo-CRCHi
17
ADA-1040PC3