8.1.2. REGISTERS ACTUAL VALUES MEASUREMENTS AND CONDITION INVERTER , READOUT
BY FUNCTION 03 (4X – REFERENCES) HOLDING REGISTERS
Address
4X
Registers
Address
Registers
description
Attribute
Value
40001
0
TypeIDH = 0x00
TypeIDL 8-bit inverter type
R
16-bit register
40002
1
Status1
Status0 16-bit inverter status
R
16-bit register
40003
2
UsolH
UsolL 16-bit solar panel voltage measurement DC
R
16-bit register
40004
3
IsolH
IsolL 16-bit solar panel current measurement DC
R
16-bit register
40005
4
FacH
FacL 16-bit network voltage frequency measurement AC
R
16-bit register
40006
5
UacH
UacL 16-bit network voltage measurement AC
R
16-bit register
40007
6
IacH
IacL 16-bit network current measurement AC
R
16-bit register
40008
7
PacH
PacL 16-bit network power measurement AC
R
16-bit register
40009
8
Hi = 0x00
EacH (Low)
R
16-bit register
40010
9
EacM
EacL 24-bit energy counter - kWh
R
16-bit register
40011
10
TempH=0x00
TempL 8-bit inverter's internal temperature
R
16-bit register
40012
11
Hi=0x00
TonH (Lo)
R
16-bit register
40013
12
TonM
TonL 24-bit operating hour counter
R
16-bit register
40014
13
Trecl/UocH
Status1, bit4=1 :
Trecl/UocL
Status1, bit4=0 :
16-bit time from reclosing / 16-bit open terminal voltage
R
16-bit register
40015
14
Hi = 0x00
Rac/Phase network impedance measurement
R
16-bit register
8.2. FRAME STRUCTURE OF MODBUS-RTU PROTOCOL
Device address (1-byte) Function (1-byte)
Dane (n-bytes)
CRC-16Lo (1-byte)
CRC-16Hi (1-byte)
8.3. USED FUNCTIONS OF MODBUS-RTU PROTOCOL
Function code
Description
03 (0x03)
Readout measurement values and Inverter state from registers MODBUS-RTU
04 (0x04)
Readout measurement values and Inverter state from registers MODBUS-RTU
14
ADA-1040PC3
Summary of Contents for ADA-1040PC3
Page 23: ...23 ADA 1040PC3...