17. Trouble shooting
Inverter does not power up:
Check that the inverter is properly inserted
Reposition inverter to verify that slot is not damaged
Check AC input present and in range (AC breakers)
Check DC input present and in range (DC breakers)
Check for loose terminations
Inverter does not start:
Check that T2S is present and properly inserted
Check remote on/off terminal
Check that manual By-pass is in normal position
Check the configuration and setting
Check threshold level
Inverter only run on AC or DC:
Check the configuration and setting
Check threshold level
no output power:
Check output breaker
All ok but I have alarm:
Check configuration file and correct no of modules
Download/clear log file
no output alarm:
mind the default time delay (uA: 60s, nuA: 30s)
Check configuration file
no information on CanDis:
Check that T2S is present and properly inserted
Check that the RJ45 cable is connected between T2S shelf and CanDis shelf
no value on TCp/Ip:
Check that the RJ45 cable is connected between T2S shelf and CanDis shelf
Wait approx 2 minutes to allow the system to collect serial data.