![CE+T Power TSI Bravo User Manual Download Page 19](http://html1.mh-extra.com/html/ce-t-power/tsi-bravo/tsi-bravo_user-manual_2577181019.webp)
8.2.6 AC input
CB per pack
CB per shelf
Cable, min
Connector
Torque
Bravo pack Single shelf
2p 32AC
3 x 6mm
2
m5
1.5nm
Bravo pack Double shelf
2p 63AC
3 x 16mm
2
+24vDC
2p 32AC
3 x 6mm
2
-48vDC to +220vDC
2p 40AC
3 x 10mm
2
8.2.7 AC output
Cable, min
Connector
Torque
Bravo pack Single shelf
3x6mm
2
m5
1.5nm
Bravo pack Double shelf
3x16mm
2
+24vDC
3x6mm
2
-48vDC to +220vDC
3x10mm
2
8.2.8 Signalling
Relay characteristics (Selectable, major, minor)
Switching power
60W
Rating
2A at 30vDC / 1A at 60vDC
max wire size
1mm
2
Digital input characteristics (Digital In 1 / 2)
Signal voltage
+5vDC (galvanic insulated)
max wire size
1mm
2
1
2
3
10
11
12
Common
Common
Common
Common
NO
NO
NO
ln 2
NC
NC
NC
ln 1
Digital 2
Digital 1
Minor (NUA)
Major (UA)
Selectable*
12
12
1
1
19
– TSI Bravo – user manual – v7.0