7. System Design
7.1 pack / A la Carte
The systems designed are divided in two topologies.
7.1.1 pack
The pACk is a pre assembled and configured single phase inverter system comprising 19”
inverter sub rack, inverter modules, monitor device and AC output distribution breaker.
The pACk is normally mounted in a 19” rack. mounting kit is included in the delivery.
The pACk is only available as single phase, -48vDC, EpC-mode.
A pACk comprises of max 6 inverter modules.
7.1.2 A la Carte
The A la Carte is pre assembled and configured as single phase or three phase systems. The system comprises cabinet, inverter
sub rack, inverter modules (+24vD to 220vDC), manual by-pass, monitor device and AC output distribution.
The A la Carte is available as EpC (Enhanced power Conversion) or REg (Regular) operation.
The A la Carte (single phase) populate 1 to 32 modules, max 80kvA (48kvA
3
)
The A la Carte (three phase) populate 3 to 30 modules, max 75kvA (45kvA
3
)
Dual input (AC and DC) inverter modules (EpC)
96% efficiency
4
at normal operation (EpC)
Always conditioned and filtered output voltage
Seamless transfer (0ms) between primary and secondary source of supply
no single point of failure
flexible AC output distribution
full modularity
full redundancy
3 | +24v version
4 | Bravo EpC -48vDC/230vAC
T2S
Blank
TSI
TSI blank
AC ooutput
15
– TSI Bravo – user manual – v7.0