![CE+T Power BRAVO ST-120 VAC-UL User Manual Download Page 26](http://html1.mh-extra.com/html/ce-t-power/bravo-st-120-vac-ul/bravo-st-120-vac-ul_user-manual_2577178026.webp)
9. Human-Machine Interface
9.1 Inverter module (Requires firmware V208.4 or higher)
=
~
=
=
=
~
AC OUT
DC IN
AC IN
Inverter Status
Output Power Status
Inverter Status LED
Description
Remedial action
OFF
No input power or forced stop
Check environment
Permanent green
Normal operation
Blinking green
Converter OK but working conditions
are not fulfilled to operate properly
Blinking green/orange
alternatively
Recovery mode after boost
(10 In short circuit condition)
Permanent orange
Starting mode
Blinking orange
Modules cannot start
Check T2S configuration or Module with wrong
firmware. Need firmware V208.4 or higher.
Blinking red
Recoverable fault
Permanent red
Non recoverable fault
Send module back for repair
Output Power (redundancy not counted)
<5%
5% to
40%
40 to
70%
80 to
95%
100%
100% =
overload
Output Power (redundancy not counted)
×
×
×
Status output power LED
×
×
×
1B
1P
2P
2P
3P
3B
Behaviour (B = Blinking and P = Permanent )
9.2 T2S ETH
•
Alarm indication on Catena (Urgent / Non Urgent / Configurable)
- Green:
No alarm
- Red:
Alarm
- Flashing Exchanging information with inverters
(only Configurable alarm)
•
Outgoing alarm relay delay time
- Major and Minor
Adjustable from 2 to 60 seconds
•
Parameter setting via Laptop.
•
Factory default according to list of set values.
Major Alarm
Ethernet Port
System Status
Minor Alarm
Micro SD Card
Human-Machine Interface
26
- Bravo ST 120 Vac - 2+1 Redundancy - User Manual - v1.0
Summary of Contents for BRAVO ST-120 VAC-UL
Page 38: ......