7. Accessories
7.1 Monitoring - T2S ETH (Included)
The T2S ETH is an interface giving access to the TSI modules that are connected together in any TSI systems.
The T2S ETH doesn’t perform any control or management of the TSI system. It can be removed, replaced or moved to
another live system without affecting the original TSI system operation nor the target system.
7.1.1 Parameters setting
The T2S ETH supports IPv4 network and featured with an ETH port at the front. Connected to a laptop, it enables TSI
system settings, modules and phase assignments, and other various adjustments to allow TSI best fit with actual site
conditions.
(Operation of T2S ETH is described in separate manual available on request)
7.1.2 System diagnostic and troubleshooting
The T2S ETH is featured with a built-in user interface to allow on-line diagnostic through the laptop.
Installers and maintenance technicians should always carry a proper laptop to access/reconfigure the system on-site.
(Operation of T2S ETH is described in a separate manual available on request)
7.1.3 Monitoring
The T2S ETH monitors max of 32 system modules.
The T2S ETH is featured with
•
3 digital output alarm contacts.
•
2 digital input contacts.
•
MODBUS.
•
Alarm monitoring.
•
Log file of the latest 2000 events as FIFO.
•
SNMP v1 through T2S ETH.
•
SNMP v2c and v3 through Catena (If T2S ETH is connected to Catena).
•
Power: 2 W
•
Part Number
48 Vdc Model:
T322010100
110 Vdc Model:
T322051000
Accessories