![CE+T Power BRAVO ST-120 VAC-UL User Manual Download Page 23](http://html1.mh-extra.com/html/ce-t-power/bravo-st-120-vac-ul/bravo-st-120-vac-ul_user-manual_2577178023.webp)
8.3.7 AC Input (AC Input protection mandatory)
Model
Breaker
Cable Min
Cable Max
Torque
lb.in
48 VDC
60 A / 1P
1 X 4 AWG
1 X 2 AWG
24.9 - 26.7
110 VDC
8.3.8 AC Output
Model
Cable Min
Cable Max
Torque
lb.in
NEMA Receptacles 5 - 15R
14 AWG
NA
NA
NEMA Receptacles 5 - 20R
12 AWG
Bulk Output
1 X 4 AWG
1 X 2 AWG
24.9 - 26.7
8.3.9 Signalling
Relay characteristics (Selectable, Major, Minor)
•
Switching power
60 W
•
Rating
2 A at 30 Vdc / 1 A at 60 Vdc
•
Max wire size
1 mm
2
Digital input characteristics (Digital IN 1/2)
•
Signal voltage
+5 Vdc (galvanically insulated)
•
Max wire size
1 mm
2
Note: In this system Remote ON/OFF function is not accessible to the customer connection.