3.3.2 Network Variable Summary
Variable Name
Variable Type
Default
Description
Node Object (#0)
nviRequest
SNVT_obj_request
0, normal
Object request (object_id,request)
nvoStatus SNVT_obj_status
Object
status
nviTimeSet
SNVT_time_stamp
Time of day (yr,mn,dy,hr,mn,sec)
nvoAlarm SNVT_alarm
WattNode
alarms
nciStsMaxSendT SNVT_elapsed_tm
0
sec.
Status update interval (dy,hr,mn,sec,ms)
Energy Measurement Object (#1)
nvoElecWH_f
SNVT_elec_whr_f
Energy (floating point watt-hours)
nvoElecKWH SNVT_elec_kwh
Energy (0–65535 kilowatt-hours)
nvoEngyClrT
SNVT_time_stamp
Energy clear time (yr,mn,dy,hr,mn,sec)
nciGain
SNVT_muldiv
?, 65535
Calibration value (multiplier, divisor)
nciCTAmps
SNVT_amp
5.0 A
CT rated current (0–3276.7 amps)
nciWHMaxSendT SNVT_elapsed_tm 5
sec.
Time between energy updates: 0–18 hrs.
Power Measurement Object (#2)
nvoPower_f SNVT_power_f
Instantaneous power (floating point watts)
nvoPowerW SNVT_power
Instantaneous power (0–6553.5 W)
nvoPowerKW SNVT_power_kilo
Instantaneous power (0–6553.5 KW)
nciWMaxSendT SNVT_elapsed_tm
10
sec. Maximum time between power updates: 0–
18 hrs. (dy,hr,mn,sec,ms)
nciWMinSendT SNVT_elapsed_tm
0
sec. Minimum time between power updates: 0–18
hrs. (dy,hr,mn,sec,ms)
nciWMinDelta
SNVT_power_f
1.0e38 W
Amount by which power must change to
force an output transmission
nciPowLimHi
SNVT_power_f
1.0e38 W
Power alarm high limit
nciPowLimLo
SNVT_power_f
0.0 W
Power alarm low limit
nciPowAlmSetT
SNVT_elapsed_tm
0 sec.
Power alarm set time: 0–18 hrs.
nciPowAlmClearT SNVT_elapsed_tm 0
sec.
Power alarm clear time: 0–18 hrs.
nciPowLimHystHi SNVT_power_f
0.0
W
Power alarm high hysteresis
nciPowLimHystLo SNVT_power_f
0.0
W
Power alarm low hysteresis
nciPowAlarmInhT SNVT_elapsed_tm 0
sec.
Initial power alarm inhibit time: 0–18 hrs
(dy,hr,mn,sec,ms)
Demand Measurement Object (#3)
nvoDemand_f
SNVT_power_f
Demand power (floating point watts)
nvoDemandW SNVT_power
Demand power (0–6553.5 W)
nvoDemandKW
SNVT_power_kilo
Demand power (0–6553.5 KW)
nvoPkDemand_f SNVT_power_f
Peak demand power
nvoPkDemandW SNVT_power
Peak demand power (0–6553.5 W)
nvoPkDemandKW SNVT_power_kilo
Peak demand power (0–6553.5 KW)
nvoPkDemResetT
SNVT_time_stamp
Peak demand reset time (dy,hr,mn,sec,ms)
nvoPeakDemT
SNVT_time_stamp
Peak demand time (dy,hr,mn,sec,ms)
nvoLoadControl
SNVT_switch
Demand alarm load control (on/off)
nciDemHiLim1
SNVT_power_f
1.0e38
Demand power alarm high limit 1
nciDemHiLim2
SNVT_power_f
1.0e38
Demand power alarm high limit 2
nciDemPeriod
SNVT_elapsed_tm
15 min.
Demand period: 1–720 min.
(dy,hr,mn,sec,ms)
nciDemSubints SNVT_count 1
Demand subintervals (1–15)