Operation
27
4.4 Demand Measurement
Demand Measurement
Object #3
Demand
Outputs
Configuration
Properties
nciDemPeriod SNVT_elapsed_tm
nciDemSubints SNVT_count
nvoDemandW SNVT_power
nvoDemandKW SNVT_power_kilo
nvoLoadControl SNVT_switch
nvoPkDemandW SNVT_power
nvoPkDemandKW SNVT_power_kilo
nvoPkDemand_f SNVT_power_f
nvoPeakDemT SNVT_time_stamp
nvoPkDemResetT SNVT_time_stamp
nvoDemand_f
SNVT_power_f
nv1
nciDemHiLim1 SNVT_power_f
nciDemHiLim2 SNVT_power_f
nc9
nc10
Manufacturer
Specific
Variables
Figure 4.5: Demand Measurement Object
Demand is defined as the average power over a specified time interval. Typical demand intervals are 5, 10,
15, 30, 60, etc. up to 720 minutes, but the WattNode supports arbitrary demand intervals from 1 to 720
minutes. The WattNode records the peak demand with time stamp for metering applications where the
measurements may only be accessed weekly or monthly.
Power (watts)
Demand
Interval
Demand
Interval
Demand
Interval
Demand
Interval
Demand
Interval
Power
Curve
Demand
Figure 4.6: Demand Measurement