background image

2

IOM-8311HP/LP

SECTION III

2.  If the regulator and system are to both be shut down, 

slowly close the inlet (upstream) block valve.  Close the 
outlet (down stream) valve only if regulator re mov al is 
re quired.

Do not walk away and leave a bypassed regulator 
unattended!

V. SHUTDOWN

1.  On systems with a bypass valve, and where system 

pressure is to be maintained as the reg u la tor is shut 
down, slowly open the bypass valve while closing the inlet 
(up stream) block valve.  Fully close the inlet (up stream) 
block valve.  (When on bypass, the system pres sure 
must be con stant ly ob served and manually regulated.)  
Close the outlet (downstream) block valve.

         

     

SECTION V

IV.  START-UP

1.  Start with the block valves closed.  A bypass valve may 

be used to maintain inlet pressure in the upstream 
system without chang ing the fol low ing steps.

2.  Relax the range spring by turning the adjusting screw 

counter clockwise (CCW) (viewed from above)  a min-
 i mum of three (3) full revolutions.  This re duc es the inlet 
(upstream) pres sure set point.

3.  If it is a “hot” piping system, and equipped with a bypass 

valve, slowly open the bypass valve to preheat the sys-
tem piping and to allow slow ex pan sion of the piping.  
Ensure proper steam trap operation, if installed.  Close ly 
monitor inlet (upstream) pressure via gauge to ensure 
not over-pres sur iz ing.  

NOTE:

 

 If no bypass valve is 

in stalled, extra caution should be used in starting up a 
cold system; i.e. do everything slowly.

4.  Crack open the inlet (upstream) block valve.

5.  Slowly open the outlet (downstream) block valve ob-

 serv ing the inlet (upstream) pressure gauge.  De ter mine if 
the regulator is 

fl

 owing.  If not, slowly rotate the regulator 

adjusting screw counter clock wise (CCW) (viewed from 
above) until 

fl

 ow be gins.

6.  Continue to slowly open the outlet (downstream) block 

valve until fully open.

7.  Observing the inlet (upstream) pressure gauge, rotate 

the adjusting screw clockwise (CW) slowly until the inlet 
pressure begins to rise.  Rotate CW until the desired 
setpoint is reached.

8.  Continue to slowly open the inlet (upstream) block valve.  

If the inlet (upstream) pressure exceeds the desired 
setpoint pressure, rotate the adjusting screw CCW until 
the pressure decreases.

9. When 

fl

 ow is established steady enough that both the 

outlet and inlet block valves are fully open, begin to 
slowly close the bypass valve, if in stalled.  

10. Develop system 

fl

 ow to a level near its expected normal 

rate, and reset the regulator setpoint by turning the 
adjusting screw CW (viewed from above) to increase 
inlet pressure, or CCW to reduce inlet pressure.

11. Reduce system 

fl

 ow to a minimum level and observe 

setpoint.  Inlet pressure will rise from the set point of Step 
10.  The maximum rise in outlet pressure on decreas-
ing 

fl

 ow should not exceed the stated upper limit of the 

range spring by greater than 10%; i.e. 10-40 psig (.69-
2.76 Barg) range spring, at low 

fl

 ow the outlet pressure 

should not exceed 44 psig (3 Barg).  If it does, consult 
factory.

SECTION IV

III.  PRINCIPLE OF OPERATION

1.  Movement occurs as pressure variations register on 

the diaphragm.  The registering pressure is the inlet 
P

1

, or upstream pressure.  The range spring opposes 

di a phragm movement.  As inlet pressure drops, the range 

spring pushes the di a phragm down, closing the ports; 
as inlet pres sure increases, the di a phragm push es up 
and the ports open.

2.  A complete diaphragm failure will cause the reg u la tor 

to fail closed.

11.  Regulators are not to be direct buried un der ground.

12.  For insulated piping systems, recommendation is to not 

insulate regulator.

10.  Basic Regulator - (Refer to Figure 1):  Regulator may 

be rotated around the pipe axis 360°. Rec om mend ed 
position is with spring chamber ver ti cal upwards.  Orient 
such that the spring chamber vent hole does not collect 
rainwater or debris.

CAUTION

Summary of Contents for 8311LP

Page 1: ...uid gaseous or steam service Refer to Technical Bulletin 8311 TB for design conditions and selection recom mendations This is not a safety device and must not be substituted for a code approved pressu...

Page 2: ...til fully open 7 Observing the inlet upstream pressure gauge rotate the adjusting screw clockwise CW slowly until the inlet pressure begins to rise Rotate CW until the desired setpoint is reached 8 Co...

Page 3: ...de optimum free vertical movement 8 Pryloosepressureplate 22 fromdiaphragm s 20 andremoveboth Inspecttoensurenodeformation due to over pressurization If deformed replace NOTE 1 Not removing the pusher...

Page 4: ...ttern that allows bottom flange 3 to be brought up evenly Refer to Step 11 for recommended torques Regulator Size Torque Bolt Size 1 1 2 2 50 ft lbs 68 N M 1 2 3 4 50 ft lbs 68 N M 5 8 NOTE Never repl...

Page 5: ...ange Contact factory adjusting screw does not allow bringing pressure to a stable and proper level C Too much build C1 Review build expected C2 Contact factory D Restricted diaphragm movement D Ensure...

Page 6: ...tminimum parts required for inspection and rebuild Soft Goods Kit Those in column B include minimum trim replacement parts needed plus those Soft Goods parts from column A If the BOM is not available...

Page 7: ...aphragm 21 Diaphragm Gasket 22 Pressure Plate 24 Pressure Plate Nut 25 Diaphragm Ring 27 Spring Button 28 Range Spring 29 Flange Bolt 30 Flange Nut 31 Nameplate 32 Adjusting Screw or Handwheel Assembl...

Page 8: ...hco com Printed in U S A IOM 8311HP LP Cashco GmbH Handwerkerstrasse 15 15366 Hoppegarten Germany PH 49 3342 4243135 Fax No 49 3342 4243136 www cashco com Email germany cashco com Cashco do Brasil Ltd...

Reviews: