10
CV072018-1
DEFAULT
By selecting this menu item and pressing the OK button, the parameters for the management of the unit are automatically assigned the
preset values:
Program valid from Monday to Friday:
Program valid from Saturday to Sunday:
TIME TABLE
Time table
Speed fans/ air flow/ pressure
Air after-treatment condition: (ON enabled, OFF inhibited)
C1 00:00 -> 06:29
medium
OFF
C2 06:30 -> 07:59
medium
ON
C3 08:00 -> 11:29
low
ON
C4 11:30 -> 12:59
High
ON
C5 13:00 -> 17:59
low
ON
C6 18:00 -> 21:59
high
ON
C7 22:00 -> 00:00
medium
OFF
C8 not used
-
-
TIME TABLE
Time table
Speed fans/ air flow/ pressure
Air after-treatment condition: (ON enabled, OFF inhibited)
C1 00:00 -> 07:29
medium
OFF
C2 07:30 -> 07:59
medium
ON
C3 08:00 -> 11:29
medium
ON
C4 11:30 -> 12:59
high
ON
C5 13:00 -> 17:59
medium
ON
C6 18:00 -> 21:59
high
ON
C7 22:00 -> 00:00
medium
OFF
C8 not used
-
-
SPEED LEVELS
Low: Medium sp.
OFF
Medium sp.:
030%
if the unit is equipped with adjustable speed fans; 1 if the unit is equipped with three-
speed fans; auto if the unit has a CO2 sensor, relative humidity or if it is managed by an external
0-10V signal.
0200m s\h
if the unit is of constant flow with cop \ cav kit. This value also depends on the factory
menu settings based on the performance of the unit.
010Pa
if the unit is constant pressure with cop \ cav kit. This value also depends on the factory
menu settings based on the performance of the unit.
High speed:
065%
if the unit is equipped with adjustable speed fans; 2 if the unit is equipped with three-
speed fans; auto if the unit has a CO2 sensor, relative humidity or if it is managed by an external
0-10V signal.
20000m s\h
if the unit is of constant flow with kit cop\ cav. This value also depends on the fac-
tory menu settings based on the performance of the unit.