background image

4

Step 4 — Install Barometric Bypass Damper

The barometric bypass damper is a critical part of Carrier 3--Zone
System for controlling noise at minimum airflow. A barometric

bypass should be installed unless the duct work and indoor unit

have been sized for use without a bypass. When a direct bypass
(outlet air fed back directly into the return) is used, bypassing

decreases entering air temperature in cooling and increases it in
heating. Excessive bypassing will lead to limit trips, either through

the LAT/HPT sensor or the equipment internal limits.

Step 5 — Install Leaving Air Temperature (LAT)

Sensor / Heat Pump Temperature (HPT) Sensor

(optional)

The Leaving Air Temperature (LAT) sensor is used to detect a
cooling overload condition and is connected to the LAT and LATC

terminals. Polarity does not matter. Locate LAT sensor in main
supply trunk after heating and cooling coil and before bypass

damper and first branch. Cycling on internal equipment limits is to

be avoided because it over stresses and can shorten the life of the
equipment. The LAT limit setting should be selected to trip below

the equipment limit.

Fig. 5 -- Leaving Air Temperature (LAT) Sensor / Heat Pump

Temperature (TPT) Sensor optional

The HPT sensor is used with ZONECC3ZHP01 to detect a cooling
overload condition and is connected to the HPT and HPTC

terminals. The HPT sensor will also be monitored in heating to
detect a heating overload condition at the coil with a shutdown

temperature of 115

_

F. It can be installed through the wall of the fan

coil or may be located entirely inside the fan coil near the blower
inlet being careful that it does not interfere with the blower wheel.

If the HPT sensor is not used, the 10K ohm resistor attached to the
2 HPT terminals on the board must be left in place.

NOTE

: ZONECC3ZAC01 model

does not have HPT connector.

Fig. 6 -- Leaving Air Temperature (LAT) Sensor

Please refer to

Limit Temperature Levels and Actions Table

in

the Installation and Start--Up Instructions for additional

information on the response of the system to LAT/HPT sensors.

Step 6 — Connect the Power Supply

Optional:

Use a dedicated 24 VAC, 40 VA, 60 Hz isolated

transformer (not included).
Otherwise, if the cooling and heating systems have separate
transformers, twist off the

Rc/Rh

jumper using a pair of long nosed

pliers. Then connect the R of the cooling transformer to Rc, the R

of the heating transformer to Rh and the common of both
transformers to C. Connect a jumper wire between Rz and Rc. Rc

powers G,Y, and O outputs. Rh power W outputs.

Fig. 7 -- Connecting the Power Supply

Step 7 — Wire the HVAC Equipment

The descriptions below and Table 1 will help you choose the

connect wiring diagram for your system. Table 1 also shows the
proper setting of dipswitches 9 and 10 for each diagram.
There are 8 dipswitch settings on the AC zone control and an

additional 4 dipswitch on the HP zone controls board. Table 1
summarizes their function and available settings.

Fig. 8 -- Dip Switches

Summary of Contents for ZONECC3ZAC01

Page 1: ...peration when utilizing a heat pump S Max Cycle Rate Allows 4 equipment cycles per hr cph providing maximum equipment protection S Selection Jumpers Designed for easy configuration S Additional Options S Timeguard override S Compressor protection S Modulating damper control in emergency situations S Damper fuse protection S High and low temperature limits S Auto changeover from any zone S RH and R...

Page 2: ...tuator required 3 conductors S The connection to thermostat and equipment furnace or fan coil could require as many as 8 conductors for a multi state installation S The Leaving Air Temperature LAT and Heat Pump Temperature HPT used with heat pumps only sensors require 2 conductors each S Cables with excess conductors are acceptable Step 1 Mounting the Carrier 3 Zone System The Carrier 3 Zone Syste...

Page 3: ...3 Thermostat Wiring Example Zone 1 Zone 2 Fig 3 Wiring Diagram for Installation of Thermostats Fig 4 Installing Dampers ...

Page 4: ...g to detect a heating overload condition at the coil with a shutdown temperature of 115_F It can be installed through the wall of the fan coil or may be located entirely inside the fan coil near the blower inlet being careful that it does not interfere with the blower wheel If the HPT sensor is not used the 10K ohm resistor attached to the 2 HPT terminals on the board must be left in place NOTE ZO...

Page 5: ...T energized with G OFF W energized with G ON 7 Sets Leaving air Temperature LAT limit temperature HP 2 Stage control only 145_F OFF OFF 160_F ON 175_F ON 8 130_F ON OFF 9 Designated Zoning Controller connection to heat pump HP or an air conditioner AC 1 or 2 Speed HP 1 Stage Aux Heat OFF 1 or 2 Speed AC 1 or 2 Stage Heat1 ON 1 Speed HP 1 Stage Aux Heat2 OFF 10 Designates the type of thermostat use...

Page 6: ...AT EQIUPMENT POWER FURNACE OR FAN COIL AIR CONDITIONER COOL LO HEAT FAN R C Y Y2 G Rz C HI HEAT R C Y1 G W1 Y2 W2 O SWITCH 9 ON SWITCH 10 ON R C Y1 G W1 Y2 W2 O R C Y G W2 C Y A04197 HP 2S 3 Zone Control AC Stat 1 Stg AC with 1 or 2 Stg Heat H P 2S 3 ZONE CONTROL ZONE 1 INPUT ZONE 1 AC TSTAT EQIUPMENT POWER FAN COIL HEAT PUMP COOL HP HEAT FAN R C Y Y2 G Rz C AUX HEAT R C Y1 G W1 Y2 W2 O SWITCH 9 O...

Reviews: