background image

2

COMPONENT LOCATION AND WIRING

CONSIDERATIONS

Locating Carrier 3--Zone System

All wiring is connected back to the Carrier 3--Zone System. Select
a location near the furnace or fan coil where wiring from each

thermostat, each damper actuator, and the equipment itself can
come together easily.
The Carrier 3--Zone System is approved for indoor use only and
should never be installed with any of its components exposed to

the elements. It may be installed in any area where the temperature

remains between 32

_

and 158

_

F, and there is no condensation. The

cover must be installed to prevent damage from other sources. Do

not locate where it will be accessible to children. Remember that
wiring access is likely the most important consideration.

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury

or death.
Turn off unit before routing control wiring or any service

operation. Remember, there may be more than one power

supply to unit.

WARNING

!

EQUIPMENT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage.
To prevent possible damage to Carrier 3--Zone System, do

not mount control on plenum, duct work, or flush against

furnace.

CAUTION

!

WIRING CONSIDERATIONS

S

All wiring in the Carrier 3--Zone system may be unshielded

S

Ordinary thermostat wire is ideal

S

Use 22 gage or larger for normal wiring

S

Lengths over 100 ft should use 20 gage or larger wire

S

Each damper actuator required 3 conductors

S

The connection to thermostat and equipment (furnace or fan
coil) could require as many as 8 conductors for a multi--state
installation

S

The

Leaving Air Temperature (LAT)

and

Heat Pump

Temperature (HPT)--

(used with heat pumps only) sensors

require 2 conductors each

S

Cables with excess conductors are acceptable

Step 1 — Mounting the Carrier 3--Zone System

The Carrier 3--Zone System can be mounted in either vertical or

horizontal position near the HVAC system inside the home. It is

designed so that wires can enter it from behind, above, or below.
Plan wire routing before mounting.

Fig. 2 -- Mounting the System

1. Remove the front cover from the base and use the base as a

template to mark drilling locations on the wall, stud , or roof
truss.

2. Mount using 4 screws (and wall anchors) provided. (See

Fig. 2.)

3. Level for appearance and tighten screws.

Step 2 — Install Thermostats in each desired Zone

Location

1. Install each thermostat according to the manufacturer’s in-

structions in their designated Zone location.

2. Connect the thermostats wires to their respective Zone des-

ignation on the right side of the the 3--Zone Panels. (See

Fig. 3).

Step 3 — Install Zone Dampers

Each damper has 3 connections:

Close (CLS), Open (OPN),

and

Common (COM).

Find the connection points along the lower left

side of the 3--Zone Control. Suggested colors are CLS = RED;

OPN = GREEN, COM = WHITE. Field label and make the

connections at the dampers and at the 3--Zone Control. Be careful
not to cross zone numbers.
If duct work required multiple dampers for a single zone, up to 5
dampers may be wired in

parallel

and may be installed in any

position.

Summary of Contents for ZONECC3ZAC01

Page 1: ...peration when utilizing a heat pump S Max Cycle Rate Allows 4 equipment cycles per hr cph providing maximum equipment protection S Selection Jumpers Designed for easy configuration S Additional Options S Timeguard override S Compressor protection S Modulating damper control in emergency situations S Damper fuse protection S High and low temperature limits S Auto changeover from any zone S RH and R...

Page 2: ...tuator required 3 conductors S The connection to thermostat and equipment furnace or fan coil could require as many as 8 conductors for a multi state installation S The Leaving Air Temperature LAT and Heat Pump Temperature HPT used with heat pumps only sensors require 2 conductors each S Cables with excess conductors are acceptable Step 1 Mounting the Carrier 3 Zone System The Carrier 3 Zone Syste...

Page 3: ...3 Thermostat Wiring Example Zone 1 Zone 2 Fig 3 Wiring Diagram for Installation of Thermostats Fig 4 Installing Dampers ...

Page 4: ...g to detect a heating overload condition at the coil with a shutdown temperature of 115_F It can be installed through the wall of the fan coil or may be located entirely inside the fan coil near the blower inlet being careful that it does not interfere with the blower wheel If the HPT sensor is not used the 10K ohm resistor attached to the 2 HPT terminals on the board must be left in place NOTE ZO...

Page 5: ...T energized with G OFF W energized with G ON 7 Sets Leaving air Temperature LAT limit temperature HP 2 Stage control only 145_F OFF OFF 160_F ON 175_F ON 8 130_F ON OFF 9 Designated Zoning Controller connection to heat pump HP or an air conditioner AC 1 or 2 Speed HP 1 Stage Aux Heat OFF 1 or 2 Speed AC 1 or 2 Stage Heat1 ON 1 Speed HP 1 Stage Aux Heat2 OFF 10 Designates the type of thermostat use...

Page 6: ...AT EQIUPMENT POWER FURNACE OR FAN COIL AIR CONDITIONER COOL LO HEAT FAN R C Y Y2 G Rz C HI HEAT R C Y1 G W1 Y2 W2 O SWITCH 9 ON SWITCH 10 ON R C Y1 G W1 Y2 W2 O R C Y G W2 C Y A04197 HP 2S 3 Zone Control AC Stat 1 Stg AC with 1 or 2 Stg Heat H P 2S 3 ZONE CONTROL ZONE 1 INPUT ZONE 1 AC TSTAT EQIUPMENT POWER FAN COIL HEAT PUMP COOL HP HEAT FAN R C Y Y2 G Rz C AUX HEAT R C Y1 G W1 Y2 W2 O SWITCH 9 O...

Reviews: