background image

Step 2—Component Location and Wiring
Considerations

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury
or death.
Turn off unit before routing routing control wiring or any
service operation. Remember, there may be more than one
power supply to unit.

All wiring must comply with national, local, and state codes.

LOCATING CARRIER 3-ZONE SYSTEM — All wiring is run
back to the Carrier 3-Zone System. Select a location near the
furnace or fan coil where wiring from each thermostat, each
damper actuator, and the equipment itself can come together
easily.

The Carrier 3-Zone System is approved for indoor use only and
should never be installed with any of its components exposed to
the elements. It may be installed in any area where the temperature
remains between 32° and 158°F, and there is no condensation. The
cover must be installed to prevent damage from other sources. Do
not locate where it will be accessible to children. It may be
mounted in either vertical or horizontal position. Remember that
wiring access is likely the most important consideration.

EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage.
To prevent possible damage to Carrier 3-Zone System, do not
mount control on plenum, duct work, or flush against furnace.

LOCATING THERMOSTATS — For proper operation, each
thermostat must accurately measure the temperature within its
zone.

For accurate temperature measurement, the following guidelines
should be followed:

Thermostat should be mounted:

Approximately 5 ft. (1.5m) from floor.

Close to the center of its zone, preferably on an inside wall.

On a section of wall without pipes or duct work.

Thermostat should NOT be mounted:

Close to a window, on an outside wall, or next to a door leading
to the outside.

Where it will be exposed to direct light and heat from a lamp,
sun, fireplace, or other temperature radiating object which may
cause a false reading.

Close to or in direct airflow from supply registers and return-air
grilles.

In areas with poor air circulation, such as behind a door or in
an alcove.

WIRING CONSIDERATIONS — All wiring in the Carrier Three-
Zone system may be unshielded. Ordinary thermostat wire is ideal.
Use 22 gage or larger for normal wiring. Lengths over 100 ft.
should use 20 gage or larger wire.

Each damper actuator requires 3 conductors. The connection to
thermostats and equipment (furnace or fan coil) could require as
many as 8 conductors for a multi-stage installation. The leaving air
temperature (LAT) and heat pump temperature (HPT)—(used with
heat pumps only) 
sensors require 2 conductors each.

Cables with excess conductors are acceptable. Cut off or fold back
and tape any unneeded conductors.

Plan the routing of wiring early to avoid possible problems later
on.

Remember all wires converge at the Carrier 3-Zone system, so its
location is important.

Step 3—Install Components

INSTALL CARRIER 3-ZONE SYSTEM

The Carrier 3-Zone System is designed so that wires can enter it
from behind, above, or below. Plan wire routing before mounting.

1. Open door to access eight mounting screw slots

2. Mount to wall using four screws and wall anchors provided.

3. Level and tighten screws.

INSTALL THERMOSTATS

1. Follow manufacturer’s supplied instructions for installing

thermostats.

EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage.
Improper wiring or installation may damage the thermostats.
Check to make sure wiring is correct before proceeding with
installation or turning on unit.

Step 4—Install Zone Dampers

Proper selection and sizing of dampers is important for proper
system operation. Selection and sizing information is not provided
in this installation instruction.

If duct work requires multiple dampers for a single zone, up to 5
dampers may be wired in parallel.

Zone dampers may be installed in any position.

Install dampers so that actuator is visible for inspection and
accessible in the event it would ever need to be serviced. The black
mark on the end of damper shaft represents position of damper
blade.

The 45 degree actuators on round ducts have their mechanical
stops set at 45 degrees. DO NOT CHANGE THIS SETTING.
Doing so will allow the actuator to close when it is trying to open.
If an actuator is removed, it must be properly aligned when it is
reinstalled. Do this by rotating the actuator and the blade to their
closed positions and then tightening the actuator to the shaft. This
assures alignment at the closed position. (Pressing the blade
release button releases the motor and allows the actuator to be
manually turned.)

EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage.
When dampers are located in an unconditioned space, con-
densation is likely to occur in cooling. Regular and severe
condensation will damage the actuator. To prevent conden-
sation and losses, all dampers and ductwork in unconditioned
space must be insulated or otherwise protected.

Whenever condensation might occur, it is recommended that
plastic actuator covers (Part# DAMPACTXXCOV) be used over
the actuator. These covers can help prevent condensation on
actuators by locking out ambient humidity. Insulation may be
applied over the cover to minimize heat transfer.

To install, place the cover over actuator and seal in place over the
surrounding insulation with duct tape on all four sides. Sealing

2

Summary of Contents for ZONECC3Z

Page 1: ...ons This instruction covers the physical installation and start up of the Carrier 3 Zone system Use this instruction to guide the actual installation process after all the air side decisions have been made 1 Install in non condensing areas with ambients between 32 F and 158 F 2 A TXV is required on the indoor coil when used with all residential split system equipment 3 A separate transformer is no...

Page 2: ... conductors each Cables with excess conductors are acceptable Cut off or fold back and tape any unneeded conductors Plan the routing of wiring early to avoid possible problems later on Remember all wires converge at the Carrier 3 Zone system so its location is important Step 3 Install Components INSTALL CARRIER 3 ZONE SYSTEM The Carrier 3 Zone System is designed so that wires can enter it from beh...

Page 3: ...of flexible duct work over 1 end of zone damper See Fig 4 2 Secure flexible duct to zone damper using SMACNA or other approved method 3 Properly seal joint using duct tape mastic or other approved method Do not allow mastic to come in contact with actuator 4 Insulate damper using 1 1 2 in to 2 in insulation Check your local codes See Fig 5 NOTE All zone dampers and duct work must be properly suppo...

Page 4: ...e control and thermostat type select the appropriate wiring diagram Terminal designations on all the thermostats are those of Carrier thermostats Other brands may vary somewhat Wiring diagrams and 3 Zone Control board layouts are located at the end of this Installation Instruction Fig 8 Shows the board layout for the AC Control Fig 9 Shows the board layout for the HP 2S Control Fig 10 Shows the 3 ...

Page 5: ... Y and O outputs Rh powers W outputs Fig 8 AC or 1 Stage System Wiring Diagram A04192 Rh Rc Y1 W1 G R C Y1 W1 G R C Y1 W1 G R C Y1 W1 G CLS_1 COM_1 OPN_1 CLS _ 2 COM_2 OPN_ 2 CLS _ 3 COM_3 OPN_ 3 C Rz LA TC LA T ON 1 2 3 4 5 6 7 Rela y Rela y Rela y Fus e Triac Triac Triac Triac Triac Triac Power Supply Micro W Y1 G Damper 1 Damper 2 Damper 3 Compressor Timer Override Status Rc Rh Twist Of f Zone ...

Page 6: ...ing on until the first mode has been satisfied for the selected time Timer Override A momentary switch is located near the bottom of the control circuit board Pressing it momentarily overrides all of the system timers allowing the control to immediately jump to the highest calling stage Temperature Limits and Sensors Both the AC and HP controls have a LAT leaving air temperature sensor which is to...

Page 7: ... on the AC zone control and an additional 4 on the HP board Below is a table summarizing their function Below the table is a more detailed description of what each does and how to set it properly for your application Dipswitches Dipswitch 1 This determines whether or not a minimum time must pass before the control is allowed to transition between heating and cooling or vice versa If it is set to O...

Page 8: ... be used or the system may be checked out manually by creating thermostat calls When using thermostats remember that only the calling zoning dampers will be open This provides the means to select which dampers are open for any heating or cooling call It is advisable that the initial checkout be made with all dampers open before the bypass is set This can be done by temporarily setting Switch 5 to ...

Page 9: ...AN COIL AIR CONDITIONER COOL LO HEAT FAN R C Y Y2 G Rz C HI HEAT R C Y1 G W1 Y2 W2 O SWITCH 9 ON SWITCH 10 ON R C Y1 G W1 Y2 W2 O R C Y G W2 C Y Fig 11 HP 2S 3 Zone Control AC Stat 1 Stg AC with 1 or 2 Stg Heat A04197 H P 2S 3 ZONE CONTROL ZONE 1 INPUT ZONE 1 AC TSTAT EQIUPMENT POWER FAN COIL HEAT PUMP HT AND CL AUX HT FAN R C Y Y2 G Rz C REV VALVE R C Y1 G W1 Y2 W2 O SWITCH 9 OFF SWITCH 10 OFF Rh...

Page 10: ...FAN COIL LO COOL LO HEAT FAN R C G Rz C HI HEAT R C Y1 G W1 Y2 W2 O SWITCH 9 ON SWITCH 10 ON Rh Y1 G W1 Y2 W2 O R C Y1 G C Y1 Rc R Y Y2 HI COOL Y2 W2 Y2 2 SPEED AIR CONDITIONER Fig 14 HP 2S 3 Zone Control AC Stat 2 Spd AC with 1 or 2 Stg Heat A04200 H P 2S 3 ZONE CONTROL ZONE 1 INPUT ZONE 1 2S AC TSTAT EQIUPMENT POWER FAN COIL LO HT AND CL AUX HT FAN R C G Rz C REV VALVE R C Y1 G W1 Y2 W2 O SWITCH...

Page 11: ...11 ...

Page 12: ...lus hands on the products in our labs can mean increased confidence that really pays dividends in faster troubleshooting fewer callbacks Course descriptions and schedules are in our catalog CALL FOR FREE CATALOG 1 800 644 5544 Packaged Service Training Classroom Service Training A94328 Copyright 2004 CARRIER Corp 7310 W Morris St Indianapolis IN 46231 zkit15si Manufacturer reserves the right to di...

Reviews: