background image

Connect the equipment R to both Rz and either Rh or Rc. A jumper
will be needed. Rc and Rh are internally connected but may be
separated by breaking a twist-off (see step 4 below).

Step 3—Wire Dampers

Each damper has three connections: Close, Open, and Common.
Find the connection points along the lower left side of the 3-Zone
Control. Suggested colors are Close = red; Open = green; Common
= white. Field label and make the connections at the dampers and
at the 3-Zone Control. Be careful not to cross zone numbers.

Step 4—Wire Remainder

Connect the LAT sensor to the LAT and LATC terminals. Polarity
does not matter. If used, connect the HPT sensor to the HPT and
HPTC terminals. If the HPT sensor is not used, you must leave the
10K ohm resistor connected in its place.

If the cooling and heating systems have separate transformers,
twist off the Rc/Rh jumper using a pair of long nosed pliers. Then
connect the R of the cooling transformer to Rc, the R of the heating
transformer to Rh and the common of both transformers to C.
Connect a jumper wire between Rz and Rc. Rc powers G, Y, and
O outputs. Rh powers W outputs.

Fig. 8—AC or 1-Stage System Wiring Diagram

A04192

 Rh
 Rc

 Y1
 W1

 G

 R

 C

 Y1
 W1

 G

 R

 C

 Y1
 W1

 G

 R

 C

 Y1
 W1

 G

 CLS_1
 COM_1

 OPN_1

 CLS 

_ 2

 COM_2

 OPN _ 2

 CLS 

_ 3

 COM_3

 OPN _ 3

C

Rz

LATC

LAT

ON

1    2    3    4    5    6    7

Relay

Relay

Relay

Fuse

Triac

Triac

Triac

Triac

Triac

Triac

Power Supply

Micro

W

Y1

G

Damper 1

Damper 2

Damper 3

Compressor

Timer Override

Status

Rc/Rh

Twist Of f

Zone

Zone

Zone

Dipswitches 1- 8

To  24VAC
Power

To Equipment

To  Zone 1
Damper

To  Zone 2
Damper

To  Zone 3
Damper

To LAT
Sensor

To 

 

Zo

ne

Thermostat

To 

 

Zon

e

Thermostat

To  Zone
Thermostat

Programming

Connecto

r

Fig. 9—HP or 2-Stage System Wiring Diagram

A04191

 Rh

 Rc

 Y1
 W1

 G

 Y2

 W2

 O

 R

 C

 Y1
 W1

 G

 Y2

 W2

 O

 R

 C

 Y1
 W1

 G

 Y2

 W2

 O

 R

 C

 Y1
 W1

 G

 Y2

 W2

 O

 CLS_1
 COM_1

 OPN_1

 CLS 2
 COM_2

 OPN 2

 CLS 3
 COM_3

 OPN 3

C

R

HPT

HP

LATC

LAT

ON

1    2    3    4    5    6    7

1    2    3

ON

Relay

Relay

Relay

Relay

Relay

Relay

Fuse

Triac

Triac

Triac

Triac

Triac

Triac

Power Supply

Micro

W

Y1

G

W

Y2

O

Damper 1

Damper 2

Damper 3

Compressor

Timer Override

E-Heat

Status

E-Heat

Rc/R

Twist Of f

Zone

Zone

Zone

To Zone 1
Thermostat

To Zone 2
Thermostat

To Zone 3
Thermostat

To  24VAC
Power

To
Equipment

To Zone 1
Damper

To Zone 2
Damper

To Zone 3
Damper

To HPT
Sensor

To LAT
Sensor

Dipswitches 1 - 12

Connector

Prog

ramming

5

Summary of Contents for ZONECC3Z

Page 1: ...ons This instruction covers the physical installation and start up of the Carrier 3 Zone system Use this instruction to guide the actual installation process after all the air side decisions have been made 1 Install in non condensing areas with ambients between 32 F and 158 F 2 A TXV is required on the indoor coil when used with all residential split system equipment 3 A separate transformer is no...

Page 2: ... conductors each Cables with excess conductors are acceptable Cut off or fold back and tape any unneeded conductors Plan the routing of wiring early to avoid possible problems later on Remember all wires converge at the Carrier 3 Zone system so its location is important Step 3 Install Components INSTALL CARRIER 3 ZONE SYSTEM The Carrier 3 Zone System is designed so that wires can enter it from beh...

Page 3: ...of flexible duct work over 1 end of zone damper See Fig 4 2 Secure flexible duct to zone damper using SMACNA or other approved method 3 Properly seal joint using duct tape mastic or other approved method Do not allow mastic to come in contact with actuator 4 Insulate damper using 1 1 2 in to 2 in insulation Check your local codes See Fig 5 NOTE All zone dampers and duct work must be properly suppo...

Page 4: ...e control and thermostat type select the appropriate wiring diagram Terminal designations on all the thermostats are those of Carrier thermostats Other brands may vary somewhat Wiring diagrams and 3 Zone Control board layouts are located at the end of this Installation Instruction Fig 8 Shows the board layout for the AC Control Fig 9 Shows the board layout for the HP 2S Control Fig 10 Shows the 3 ...

Page 5: ... Y and O outputs Rh powers W outputs Fig 8 AC or 1 Stage System Wiring Diagram A04192 Rh Rc Y1 W1 G R C Y1 W1 G R C Y1 W1 G R C Y1 W1 G CLS_1 COM_1 OPN_1 CLS _ 2 COM_2 OPN_ 2 CLS _ 3 COM_3 OPN_ 3 C Rz LA TC LA T ON 1 2 3 4 5 6 7 Rela y Rela y Rela y Fus e Triac Triac Triac Triac Triac Triac Power Supply Micro W Y1 G Damper 1 Damper 2 Damper 3 Compressor Timer Override Status Rc Rh Twist Of f Zone ...

Page 6: ...ing on until the first mode has been satisfied for the selected time Timer Override A momentary switch is located near the bottom of the control circuit board Pressing it momentarily overrides all of the system timers allowing the control to immediately jump to the highest calling stage Temperature Limits and Sensors Both the AC and HP controls have a LAT leaving air temperature sensor which is to...

Page 7: ... on the AC zone control and an additional 4 on the HP board Below is a table summarizing their function Below the table is a more detailed description of what each does and how to set it properly for your application Dipswitches Dipswitch 1 This determines whether or not a minimum time must pass before the control is allowed to transition between heating and cooling or vice versa If it is set to O...

Page 8: ... be used or the system may be checked out manually by creating thermostat calls When using thermostats remember that only the calling zoning dampers will be open This provides the means to select which dampers are open for any heating or cooling call It is advisable that the initial checkout be made with all dampers open before the bypass is set This can be done by temporarily setting Switch 5 to ...

Page 9: ...AN COIL AIR CONDITIONER COOL LO HEAT FAN R C Y Y2 G Rz C HI HEAT R C Y1 G W1 Y2 W2 O SWITCH 9 ON SWITCH 10 ON R C Y1 G W1 Y2 W2 O R C Y G W2 C Y Fig 11 HP 2S 3 Zone Control AC Stat 1 Stg AC with 1 or 2 Stg Heat A04197 H P 2S 3 ZONE CONTROL ZONE 1 INPUT ZONE 1 AC TSTAT EQIUPMENT POWER FAN COIL HEAT PUMP HT AND CL AUX HT FAN R C Y Y2 G Rz C REV VALVE R C Y1 G W1 Y2 W2 O SWITCH 9 OFF SWITCH 10 OFF Rh...

Page 10: ...FAN COIL LO COOL LO HEAT FAN R C G Rz C HI HEAT R C Y1 G W1 Y2 W2 O SWITCH 9 ON SWITCH 10 ON Rh Y1 G W1 Y2 W2 O R C Y1 G C Y1 Rc R Y Y2 HI COOL Y2 W2 Y2 2 SPEED AIR CONDITIONER Fig 14 HP 2S 3 Zone Control AC Stat 2 Spd AC with 1 or 2 Stg Heat A04200 H P 2S 3 ZONE CONTROL ZONE 1 INPUT ZONE 1 2S AC TSTAT EQIUPMENT POWER FAN COIL LO HT AND CL AUX HT FAN R C G Rz C REV VALVE R C Y1 G W1 Y2 W2 O SWITCH...

Page 11: ...11 ...

Page 12: ...lus hands on the products in our labs can mean increased confidence that really pays dividends in faster troubleshooting fewer callbacks Course descriptions and schedules are in our catalog CALL FOR FREE CATALOG 1 800 644 5544 Packaged Service Training Classroom Service Training A94328 Copyright 2004 CARRIER Corp 7310 W Morris St Indianapolis IN 46231 zkit15si Manufacturer reserves the right to di...

Reviews: