30
Resume: No limitation for frequency.
Note:
When AC is in “hold” zone for 3 minutes, the compressor frequency will rise to the higher
level.(frequency will increase twice at most)
8.4.2.2 Outdoor fan running rules
22
20
High
Low
8.4.2.3 Indoor fan running rules
In cooling mode, indoor fan runs all the time and the speed can be selected as high, medium, low and
auto.
Auto fan in cooling mode acts as follow:
4
3
High
Low
1
Medium
1.5
8.4.2.4 Condenser temperature protection
---55
<T3<60
℃
, the compressor frequency will decrease to the lower level until to F1 and then run
℃
s
at F1.If T3<54
, the compressor will keep running at the current frequency.
℃
---T3<52
, the compressor will not limit the frequency and resum
℃
e to the former frequency.
---T3>60
for 5 seconds, the compressor will stop until T3<52
.
℃
℃
8.4.2.5 Evaporator temperature protection
---T2<0
, the compresso
℃
r will stop and restart when T2
>=
5
.
℃
---0
℃≦
T2<4
, the compressor frequency will be limited and decre
℃
ased to the lower level.
Summary of Contents for xpower blue II 38KCL109313G
Page 1: ...C10 INVERTER SERIES Service Manual 2012 CSI A1 1206 ...
Page 12: ...10 5 Wiring Diagram 5 1 Indoor Unit 42KCL109313G 42KCL112313G 42KCL118313G ...
Page 13: ...11 42KCL124313G ...
Page 14: ...12 5 2 Outdoor Unit 38KCL109313G 38KCL112313G 38KCL118313G ...
Page 15: ...13 38KCL124313G ...
Page 36: ...34 9 2 Diagnosis and Solution 9 2 1 EEPROM parameter error diagnosis and solution ...
Page 37: ...35 9 2 2 Indoor unit and outdoor unit communication protection error diagnosis and solution ...
Page 40: ...38 9 2 7 High temperature protection of compressor top diagnosis and solution ...