14
6 Installation Details
6.1 Wrench torque sheet for installation
Outside diameter
Torque
Additional tightening torque
mm
inch
N.cm
N.cm
Ф6.35
1/4
1500(153kgf.cm)
1600(163kgf.cm)
Ф9.52
3/8
2500(255kgf.cm)
2600(265kgf.cm)
Ф12.7
1/2
3500(357kgf.cm)
3600(367kgf.cm)
Ф15.9
5/8
4500(459kgf.cm)
4700(479kgf.cm)
Ф19
3/4
6500(663kgf.cm)
6700(683kgf.cm)
6.2 Connecting the cables
The power cord of connect should be selected according to the following specifications sheet.
Rated current of appliance
Nominal cross-sectional area (mm²)
>3 and ≤6
0.75
>6 and ≤10
1
>10 and ≤16
1.5
>16 and ≤25
2.5
The cable size and the current of the fuse or switch are determined by the maximum current indicated
on the nameplate which located on the side panel of the unit. Please refer to the nameplate before
selecting the cable, fuse and switch.
Summary of Contents for xpower blue II 38KCL109313G
Page 1: ...C10 INVERTER SERIES Service Manual 2012 CSI A1 1206 ...
Page 12: ...10 5 Wiring Diagram 5 1 Indoor Unit 42KCL109313G 42KCL112313G 42KCL118313G ...
Page 13: ...11 42KCL124313G ...
Page 14: ...12 5 2 Outdoor Unit 38KCL109313G 38KCL112313G 38KCL118313G ...
Page 15: ...13 38KCL124313G ...
Page 36: ...34 9 2 Diagnosis and Solution 9 2 1 EEPROM parameter error diagnosis and solution ...
Page 37: ...35 9 2 2 Indoor unit and outdoor unit communication protection error diagnosis and solution ...
Page 40: ...38 9 2 7 High temperature protection of compressor top diagnosis and solution ...