41
Table 8 — Menu Structure* (cont)
LEGEND
*
Table 8 illustrates the complete hierarchy. Your menu
parameters may be different depending on your configuration.
For example, if you do not have a DCV (CO
2
) sensor, then
none of the DCV parameters appear.
† When values are displayed, pressing and holding the
or
button causes the display to automatically increment.
**
N/A = Not Applicable.
†† ERV Operation: When in cooling mode AND the conditions are
NOT OK for economizing, the ERV terminal will be energized.
In the Heating mode, the ERV terminal will be energized when
the OA is below the ERV OAT setpoint in the setpoint menu.
***
When used with communicating actuator the damper out is
reported in XX.X% open versus XX.X Vdc.
††† After 10 minutes without a command or mode change, the
controller will change to normal operation.
NOTES:
1.
STATUS
OCCUPIED — The factory-standard Occupancy
signal originates with a thermostat or other controller call for
indoor fan operation at CTB terminal G. This signal passes
through the Central Terminal Board’s OCCUPIED jumper JMP1
to the ECONO connector and to the W7220’s OCC input termi-
nal. An external timeclock or relay is re
q
uired to implement an
Occupancy schedule on the economizer damper position.
2.
STATUS
MA TEMP, SETPOINTS
MAT SET — The W7220
menu parameters and labels include designations MA, MAT and
Mixed Air for the economizer cooling control sensor. On these roof-
top units, the economizer control sensor is located downstream of
the evaporator/indoor coil in the supply fan section where this sen-
sor is designated as Supply Air Temperature (SAT) sensor.
3.
SETPOINTS
DRYBLB SET — This point is not displayed if a
Return Air (differential) temperature sensor or an Outdoor Air en-
thalpy sensor is connected.
4.
SYSTEM SETUP parameters must be configured as noted for
2-Speed unit operation:
EQUIPMENT = CONV
AUX2 IN = W
FAN SPEED = 2SPEED
MENU
PARAMETER
PARAMETER
DEFAULT
VALUE
PARAMETER
RANGE AND
INCREMENT
†
NOTES
ALARMS
(CONT)
SHUTDOWN ACTIVE
N/A
N/A
AUX2 IN is programmed for SHUTDOWN and 24 V has been applied to
AUX2 IN terminal.
DMP CAL RUNNING
N/A
N/A
DAMPER CALIBRATION ROUTINE RUNNING
If DCV Auto enable has been programmed, when the W7220 is complet-
ing a calibration on the dampers, this alarm will display. Wait until the cali-
bration is completed and the alarm will go away. Must have OA, MA and
RA sensors for DCV calibration; set up in the Advanced setup menu.
DA SENS ALM
N/A
N/A
DISCHARGE AIR TEMPERATURE SENSOR ALARM
Discharge air temperature is out of the range set in the ADVANCED
SETUP Menu. Check the temperature of the discharge air.
SYS ALARM
N/A
N/A
When AUX1-O is set to SYS and there is any alarm (e.g., failed sensors,
etc.), the AUX1-O terminal has 24 Vac out.
ACT UNDER V
N/A
N/A
ACTUATOR VOLTAGE LOW
Voltage received by actuator is below expected range.
ACT OVER V
N/A
N/A
ACTUATOR VOLTAGE HIGH
Voltage received by actuator is above expected range.
ACT STALLED
N/A
N/A
ACTUATOR STALLED
Actuator stopped before achieving commanded position.
CLO —
Compressor Lockout
ERV
—
Energy Recovery Ventilator
LCD
—
Li
q
uid Crystal Display
MA
—
Mixed Air
MAT —
Mixed Air Temperature
N/A
—
Not Applicable
OA
—
Outdoor Air
OAT —
Outdoor Air Temperature
OCC —
Occupied
RA
—
Return Air
RAT
—
Return Air Temperature
RTU
—
Rooftop Unit
SYS
—
System
Summary of Contents for WeatherMaster 50HC*A07 Series
Page 4: ...4 Fig 2 Unit Dimensional Drawing Sizes 07 09 ...
Page 5: ...5 Fig 2 Unit Dimensional Drawing Sizes 07 09 cont ...
Page 6: ...6 Fig 3 Unit Dimensional Drawing Sizes 11 and 12 ...
Page 7: ...7 Fig 3 Unit Dimensional Drawing Sizes 11 and 12 cont ...
Page 25: ...25 Fig 42 Electro Mechanical Control Wiring Diagram ...
Page 26: ...26 Fig 43 Electro Mechanical Control Wiring Diagram with Humidi MiZer System ...
Page 27: ...27 Fig 44 Typical ComfortLink Control Wiring Diagram 50HC 08 09 shown ...
Page 29: ...29 Fig 46 Typical PremierLink Control Wiring Diagram ...
Page 30: ...30 Fig 47 Typical PremierLink Control Wiring Diagram with Humidi MiZer System Option ...
Page 31: ...31 Fig 48 Typical RTU Open Controller Wiring Diagram ...
Page 32: ...32 Fig 49 Typical RTU Open Controller Wiring Diagram with Humidi MiZer System Option ...