Shipping Temperature
–40 to 150°F (–40 to 65°C)
Relative Humidity
5% to 95% RH non-condensing
Economizer Module Wiring Details
Use Fig. 51 and Tables 4 and 5 to locate the wiring termi-
nals for the Economizer module.
NOTE: The four terminal blocks are removable. Slide out each
terminal block, wire it, and then slide it back into place.
Fig. 51 — W7220 Economizer Module Terminal
Connection Labels
Table 4 — Economizer Module - Left Hand Terminal
Blocks
*
Sylk is a trademark of Honeywell International Inc.
Table 5 — Economizer Module - Right Hand
Terminal Blocks
LABEL
TYPE
DESCRIPTION
Top Left Terminal Block
MAT
MAT
20k NTC
and COM
Mixed Air Temperature Sensor (Polarity
Insensitive Connection)
OAT
OAT
20k NTC
and COM
Outdoor Air Temperature Sensor
(Polarity Insensitive Connection)
S-BUS
S-BUS
S-BUS
(Sylk
*
Bus)
Enthalpy Control Sensor
(Polarity Insensitive Connection)
Bottom Left Terminal Block
IAQ 2-10
2-10 vdc
Air Quality Sensor Input (e.g. CO
2
sensor)
IAQ COM
COM
Air Quality Sensor Common
IAQ 24V
24 vac
Air Quality Sensor 24 vac Source
ACT 2-10
2-10 vdc
Damper Actuator Output (2-10 vdc)
ACT COM
COM
Damper Actuator Output Common
ACT 24v
24 vac
Damper Actuator 24 vac Source
NA
The bottom pin is not used.
NA
AUX2-
OCC
E-GND
EXH1
AUX1-O
Y2-
Y1-
Y2-O
Y1-O
C
R
5004
88
4
8
-002
Rev. A
NA
A2
OCC
EX
A1
Y2I
Y2O
Y1I
Y1O
C
R
Cert
Prod
u
ct
C
a
liforni
a
Title 24, P
a
rt 6
HJW10
www.energy.c
a
.gov
MAT
MAT
OAT
OAT
S
-BU
S
S
-BU
S
IAQ 2-10
IAQ COM
IAQ 24V
ACT 2-10
ACT COM
ACT 24V
MA
MA
OA
OA
S
B
S
B
S
B
S
B
S
B
S
B
V
C
R
V
C
R
NA
50040
83
9-001
Rev. G
LABEL
TYPE
DESCRIPTION
Top Right Terminal Blocks
N/A
The first terminal is not used.
AUX2 I
24 vac IN
Shut Down (SD) or HEAT (W)
Conventional only
and
Heat Pump Changeover (O-B) in Heat
Pump mode.
OCC
24 vac IN
Occupied/Unoccupied Input
E-GND
E-GND
Earth Ground — System Re
q
uired
EXH1
24 vac OUT Exhaust Fan 1 Output
AUX1 O
24 vac OUT
Programmable:
Exhaust fan 2 output
or
ERV
or
System alarm output
Bottom Right Terminal Blocks
Y2-I
24 vac IN
Y2 in - Cooling Stage 2 Input from
space thermostat
Y2-O
24 vac OUT
Y2 out - Cooling Stage 2 Output to
stage 2 mechanical cooling
Y1-I
24 vac IN
Y1 in - Cooling Stage 1 Input from
space thermostat
Y1-O
24 vac OUT
Y1 out - Cooling Stage 1 Output to
stage 2 mechanical cooling
C
COM
24 vac Common
R
24 vac
24 vac Power (hot)
Summary of Contents for WeatherMaster 50HC*A07 Series
Page 4: ...4 Fig 2 Unit Dimensional Drawing Sizes 07 09 ...
Page 5: ...5 Fig 2 Unit Dimensional Drawing Sizes 07 09 cont ...
Page 6: ...6 Fig 3 Unit Dimensional Drawing Sizes 11 and 12 ...
Page 7: ...7 Fig 3 Unit Dimensional Drawing Sizes 11 and 12 cont ...
Page 25: ...25 Fig 42 Electro Mechanical Control Wiring Diagram ...
Page 26: ...26 Fig 43 Electro Mechanical Control Wiring Diagram with Humidi MiZer System ...
Page 27: ...27 Fig 44 Typical ComfortLink Control Wiring Diagram 50HC 08 09 shown ...
Page 29: ...29 Fig 46 Typical PremierLink Control Wiring Diagram ...
Page 30: ...30 Fig 47 Typical PremierLink Control Wiring Diagram with Humidi MiZer System Option ...
Page 31: ...31 Fig 48 Typical RTU Open Controller Wiring Diagram ...
Page 32: ...32 Fig 49 Typical RTU Open Controller Wiring Diagram with Humidi MiZer System Option ...