43
Fig. 59 — Conduit into Control Box (Size 16)
Fig. 60 — Conduit into Single Point Box (Size 16)
Fig. 61 — Mounting Position for Field Disconnects
(over 100A) (Size 16)
Fig. 62 — Mounting Position for Field Disconnects
(up to 100A) (Size 16)
Field power wires are connected to the unit at line-side pres-
sure lugs at the main terminal block (TB1) or at factory-
installed option non-fused disconnect switch. Max wire size is
#2 AWG (copper only). See Fig. 63.
Fig. 63 — Power Wiring Connections (Size 16)
NOTE: TEST LEADS - Unit may be equipped with short leads
(pigtails) on the field line connection points off the optional dis-
connect switch. These leads are for factory run-test purposes only;
remove and discard before connecting field power wires to unit
connection points. Make field power connections directly to line
connection pressure lugs only.
Units Without Disconnect Option
Units With Disconnect Option
2
4
6
1
3
5
L1
L2
L3
Optional
Disconnect
Switch
Disconnect factory test leads; discard.
Factory
Wiring
11
12
13
L1
L2
L3
TB1
208/230-3-60
460-3-60
575-3-60
Disconnect
per
NEC
Summary of Contents for WeatherMaker 50TC07 Series
Page 4: ...4 Fig 2 Dimensional Drawing for Units Built on and After 4 15 19 Size 07 ...
Page 5: ...5 Fig 3 Dimensional Drawing for Units Built Prior to 4 15 19 Size 07 ...
Page 6: ...6 Fig 4 Corner Weights and Clearances Size 07 ...
Page 7: ...7 Fig 5 Base Rail Details Size 07 ...
Page 8: ...8 Fig 6 Thru the Base Charts Size 07 ...
Page 9: ...9 Fig 7 Unit Dimensional Drawing Size 08 09 12 ...
Page 10: ...10 Fig 7 Unit Dimensional Drawing Size 08 09 12 cont ...
Page 11: ...11 Fig 8 Unit Dimensional Drawing Size 14 ...
Page 12: ...12 Fig 8 Unit Dimensional Drawing Size 14 cont ...
Page 13: ...13 Fig 9 Unit Dimensional Drawing Size 16 Unit ...
Page 14: ...14 Fig 9 Unit Dimensional Drawing Size 16 Unit cont ...
Page 19: ...19 Fig 14 Roof Curb Details Size 16 Unit ...
Page 26: ...26 Fig 34 50TC 07 Control Wiring Diagram ...
Page 27: ...27 Fig 35 50TC 07 Power Wiring Diagram ...
Page 28: ...28 Fig 36 50TC M08 12 Control Wiring Diagram ...
Page 29: ...29 Fig 37 50TC D E Wiring Diagram 08 14 Size Units ...
Page 30: ...30 Fig 38 Single Stage Cooling without VFD Power Wiring Diagram Sizes 08 12 ...
Page 31: ...31 Fig 39 2 Stage Cooling with VFD Power Wiring Diagram Sizes 08 12 ...
Page 32: ...32 Fig 40 2 Stage Cooling with VFD Power Wiring Diagram Size 14 ...
Page 33: ...33 Fig 41 50TC 16 Wiring Diagram ...
Page 34: ...34 Fig 42 2 Stage Cooling with VFD Power Wiring Diagram Size 16 ...
Page 35: ...35 Fig 43 50TC 07 Units Wiring Diagram with Humidi MiZer System Option ...
Page 36: ...36 Fig 44 50TC 08 14 Units Wiring Diagram with Humidi MiZer System Option ...
Page 37: ...37 Fig 45 50TC 16 Wiring Diagram with Humidi MiZer System Option ...
Page 69: ...69 Fig 97 Typical PremierLink Control Wiring Diagram Size 07 Shown ...
Page 70: ...70 Fig 98 50TC M08 12 PremierLink Control Wiring Diagram ...
Page 71: ...71 Fig 99 Typical PremierLink Control Wiring Diagram Dual Compressor Sizes 08 12 shown ...
Page 72: ...72 Fig 100 Typical PremierLink Control Wiring Diagram with Humidi MiZer System Option ...
Page 73: ...73 Fig 101 Typical RTU Open Controller Wiring Diagram 50TC 07 Units ...
Page 74: ...74 Fig 102 50TC M08 12 RTU Open Controller Wiring Diagram ...
Page 75: ...75 Fig 103 Typical RTU Open Controller Wiring Diagram 50TC D E08 14 Units ...
Page 76: ...76 Fig 104 RTU Open Controller Wiring Diagram 50TC 16 Unit ...
Page 83: ...83 Fig 113 UltraTech Scroll Compressor ...
Page 84: ......
Page 85: ......