47
Table 26 – COOLING CAPACITIES
2--STAGE COOLING
8.5 TONS
48TC09 COOLING CAPACITIES, UNIT WITH HUMIDI---MIZER SYSTEM IN SUBCOOLING MODE
TEMP (F) AIR ENT
CONDENSER (Edb)
AIR ENTERING EVAPORATOR --- CFM
2550/0.04
3400/0.05
4250/0.07
Air Entering Evaporator --- Ewb (F)
72
67
62
72
67
62
72
67
62
75
TC
119.20
107.44
96.41
126.95
114.98
103.92
131.87
119.81
109.54
SHC
50.63
63.94
77.40
59.17
76.72
94.21
66.80
88.44
108.22
kW
5.67
5.57
5.47
5.54
5.63
5.74
5.79
5.68
5.59
85
TC
110.40
99.22
88.76
117.63
106.26
95.77
122.21
110.77
101.07
SHC
42.39
56.16
70.07
50.42
68.45
86.38
57.71
79.86
99.95
kW
6.33
6.23
6.14
6.20
6.30
6.40
6.45
6.34
6.25
95
TC
101.37
90.79
80.86
108.07
97.31
87.39
112.29
101.47
92.38
SHC
33.97
48.22
62.56
41.46
60.01
78.39
48.40
71.09
91.47
kW
7.08
6.99
6.90
6.96
7.05
7.16
7.20
7.09
7.01
105
TC
92.04
82.06
72.71
98.19
88.05
78.72
102.07
91.86
83.40
SHC
25.31
40.06
54.88
32.24
51.33
70.17
38.85
62.06
82.67
kW
7.94
7.85
7.77
7.83
7.91
8.01
8.06
7.95
7.87
115
TC
82.37
73.01
64.24
87.95
78.45
69.73
91.46
81.90
74.09
SHC
16.38
31.65
46.95
22.71
42.37
61.69
28.94
52.74
73.52
kW
8.92
8.84
8.77
8.82
8.89
8.98
9.02
8.93
8.86
48TC09 COOLING CAPACITIES, UNIT WITH HUMIDI---MIZER SYSTEM IN HOT GAS REHEAT MODE
TEMP (F) AIR ENT
CONDENSER (Edb)
AIR ENTERING EVAPORATOR --- Ewb (F)
75 Dry Bulb
62.5 Wet Bulb
(50% Relative)
75 Dry Bulb
64 Wet Bulb
(56% Relative)
75 Dry Bulb
65.3 Wet Bulb
(60% Relative)
Air Entering Evaporator --- Cfm
2550
3400
4250
2550
3400
4250
2550
3400
4250
80
TC
37.61
33.13
26.77
44.74
41.60
36.46
50.96
48.99
44.93
SHC
---0.52
---0.63
---0.73
---0.46
---0.57
---0.67
---0.42
---0.53
---0.62
kW
5.88
5.68
5.44
6.13
5.97
5.76
6.35
6.24
6.06
75
TC
38.71
34.24
27.86
45.84
42.73
37.59
52.05
50.11
46.06
SHC
0.45
0.34
0.25
0.50
0.40
0.31
0.54
0.44
0.36
kW
5.68
5.47
5.22
5.94
5.78
5.56
6.18
6.07
5.88
70
TC
39.70
35.25
28.83
46.80
43.70
38.59
52.97
51.04
47.02
SHC
1.41
1.32
1.23
1.47
1.37
1.29
1.50
1.41
1.34
kW
5.65
5.42
5.24
5.97
5.79
5.53
6.26
6.13
5.91
60
TC
41.77
37.33
30.76
48.86
45.80
40.71
55.00
53.10
49.12
SHC
3.34
3.26
3.18
3.40
3.32
3.25
3.43
3.36
3.29
kW
5.42
5.15
5.17
5.80
5.59
5.30
6.16
6.01
5.75
50
TC
43.83
39.27
32.61
50.92
47.89
42.70
57.04
55.16
51.22
SHC
5.27
5.21
5.14
5.32
5.27
5.21
5.36
5.31
5.25
kW
5.18
5.15
5.17
5.62
5.39
5.05
6.04
5.87
5.59
40
TC
45.75
41.13
34.50
53.08
50.00
44.64
59.24
57.40
53.44
SHC
7.20
7.15
6.95
7.26
7.21
7.16
7.29
7.25
7.21
kW
4.79
4.98
4.80
5.25
5.01
5.23
5.68
5.51
5.21
LEGEND
Edb --- Entering Dry---Bulb
Ewb --- Entering Wet---Bulb
kW
--- Compressor Motor Power Input
Idb
--- Leaving Dry---Bulb
Iwb
--- Leaving Wet---Bulb
SHC --- Sensible Heat Capacity (1000 Btuh) Gross
TC
--- Total Capacity (1000 Btuh) Gross
NOTES
:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:
t
ldb
= t
edb
–
sensible capacity (Btuh)
1.10 x cfm
t
lwb
= Wet---bulb temperature corresponding to enthalpy of air
leaving evaporator coil (h
lwb
)
h
lwb
= h
ewb
–
total capacity (Btuh)
4.5 x cfm
Where: h
ewb
= Enthalpy of air entering evaporator coil
Summary of Contents for WeatherMaker 48TC**04
Page 22: ...22 CURBS WEIGHTS DIMENSIONS cont C10298A Fig 5 Dimensions 48TC 08 12 ...
Page 25: ...25 CURBS WEIGHTS DIMENSIONS cont A14149 Fig 9 Dimensions 48TC 14 ...
Page 27: ...27 CURBS WEIGHTS DIMENSIONS cont C14151 Fig 12 Dimensions 48TC 16 ...
Page 29: ...29 CURBS WEIGHTS DIMENSIONS cont C10772B Fig 15 Roof Curb Details 48TC 16 ...