Table 14 — Carrier VFD (Toshiba TOSVERT VF-S9) Program Parameter Values
*These settings differ from the Toshiba defaults and are required for Carrier applications.
Table 15 — Motor Electronic Thermal Protection (tHr) for Toshiba TOSVERT VF-S9 VFD
*IFM Letter refers to the 15th digit (Motor Option) of the unit model number.
PARAMETER GROUP
COMMUNICATION NO.
DESCRIPTION
CARRIER DEFAULT SETTINGS
Basic Parameters
CNOd
0003
Command Mode Selection
0*
FNOd
0004
Frequency Setting Mode Selection
1*
Fr
0008
Forward/Reverse Run Selection
1*
ACC
0009
Acceleration Time 1
10.0 sec
dEC1
0010
Deceleration Time 1
10.0 sec
FH
0011
Maximum Frequency
60.0 Hz*
UL
0012
Upper Limit Frequency
60.0 Hz*
LL
0013
Lower Limit Frequency
10.0 Hz*
Pt
0015
V/f Control Mode Selection
1*
tHr
0041
Motor Electronic Thermal Protection Level 1
See Table 15*
Sr1
0018
Preset-Speed Operation Frequency 1
60.0 Hz*
Extended Parameters
F115
0115
Input Terminal Selection 5 (S2)
14*
F116
0116
Input Terminal Selection 6 (S3)
11*
Frequency Parameters
F201
0201
VIA/II Input Point 1 Setting
20%*
F202
0202
VIA/II Input Point 1 Frequency
0.0 Hz
F203
0203
VIA/II Input Point 2 Setting
100%
F204
0204
VIA/II Input Point 2 Frequency
60.0 Hz*
Operation Mode Parameters
F300
0300
PWM Carrier Frequency
4 KHz*
F301
0301
Auto-Restart Control Selection
3*
F302
0302
Regenerative Power Ride-through Control
1*
F303
0303
Retry Selection (Number of Times)
2*
F360
0360
PI Control
1*
F362
0362
Proportional Gain
0.30
F363
0363
Integral Gain
0.20
MOTOR
STD EFFICIENCY
HIGH EFFICIENCY
HP
kW
IFM Letter*
230V Setting 380V Setting 460V Setting
IFM Letter*
230V Setting 460V Setting
5
3.73
A
83
77
83
L
90
83
7.5
5.60
B
80
88
84
M
80
84
10
7.46
C
85
75
86
N
85
88
15
11.19
D
81
98
79
P
81
79
20
14.92
E
94
—
87
Q
88
87
CC
VIA
VIB
PP
II
FM
F
R
RST
S1
S2
S3
CC
OUT
P24
TWO-WIRE
TRANSDUCER
4-20mA
-
+
FIRE SPEED
OVER-RIDE
E-STOP
LEGEND
Typical Factory Wiring
Optional Field Wiring
Fig. 58 — Toshiba TOSVERT VF-S9 VFD Factory-Installed Jumpers
Summary of Contents for WEATHERMAKER 48AJ020
Page 3: ...3 Fig 1 Roof Curb 48AJ AK020 030 and 48EJ EK024 034 Units ...
Page 4: ...4 Fig 2 Roof Curb 48AJ AK034 050 and 48EJ EK038 048 Units ...
Page 5: ...5 Fig 3 Roof Curb 48AJ AK060 and 48EJ EK054 068 Units ...
Page 97: ...97 Fig 78 Typical 48EK VAV 24 V Control Circuit ...
Page 99: ...99 Fig 80 Typical 48EK VAV 115 V Control Circuit ...
Page 100: ...100 Fig 81 Typical 48EJ CV 115 V Control Circuit ...
Page 101: ...101 Fig 82 Label Diagram Staged Gas Heat 48AJ AK AW AY020 050 and 48EJ EK EW EY024 048 Units ...
Page 102: ...102 Fig 83 Label Diagram Staged Gas Heat 48AJ AK AW AY060 and 48EJ EK EW EY054 068 Units ...