115
Tables 46-48 show the input and output channel designations.
Table 46 — I/O Channel Designations Base Module — CV
Table 47 — I/O Channel Designations Base Module — VAV
Table 48 — I/O Channel Designations Expansion Module (Field-Installed) — CV and VAV
LEGEND (Tables 46-48)
NOTE: All even numbered terminals are negative (–) polarity and all
odd numbered terminals are positive (+) polarity.
TERMINAL NO.
ASSIGNMENT
TERMINAL NO.
ASSIGNMENT
T1-2
SPT (CCN) — 10KV Thermistor
T23-25
Compressor 2 Safety — DI (24 vac)
T3-4
STO (CCN) — 10KV Thermistor
T24-25
Outside Air Enthalpy — DI (24 vac)
T5-6
OAT — 5KV Thermistor
T26-27
Economizer Pos. — AO (4-20 mA)
T7-8
SAT — 5KV Thermistor
T28-29
Heat 1 Relay — DO (24 vac)
T9-10
—
T30-29
Heat 2 Relay — DO (24 vac)
T11-12
SAT Reset — AI (4 to 20 mA)
T31-32
CV Power Exhaust 1/Modulating Power Exhaust — DO (115 vac)
T13-14
IAQ Indoor — AI (4 to 20 mA)
T33-32
CV Power Exhaust 2 — DO (115 vac)
T15-16
IAQ Outdoor — AI (4 to 20 mA)
T34-35
Condenser Fan — DO (115 vac)
T17-25
Y1 or Remote Start/Stop — DI (24 vac)
T36-35
OFC2 — DO (115 vac)
T18-25
Y2 — DI (24 vac)
T37-38
—
T19-25
W1 — DI (24 vac)
T39-38
—
T20-25
W2 — DI (24 vac)
K1
Indoor Fan Relay — DO (LV)
T21-25
G — DI (24 vac)
K2
Compr. 1 — DO (HV)
T22-25
Compressor 1 Safety — DI (24 vac)
K3
Compr. 2 — DO (HV)
TERMINAL NO.
ASSIGNMENT
TERMINAL NO.
ASSIGNMENT
T1-2
SPT (CCN) — 10KV Thermistor
T23-25
Compressor 2 Safety — DI (24 vac)
T3-4
RAT — 5KV Thermistor
T24-25
Outside Air Enthalpy — DI (24 vac)
T5-6
OAT — 5KV Thermistor
T26-27
Economizer Pos. — AO (4-20 mA)
T7-8
SAT — 5KV Thermistor
T28-29
Heat 1 Relay - DO (24 v)
T9-10
—
T30-29
Heat Interlock Relay — DO (24 v)
T11-12
SAT Reset — AI (4 to 20 mA)
T31-32
Modulated Power Exhaust — DO (24 vac)
T13-14
IAQ Indoor — AI (4 to 20 mA)
T33-32
—
T15-16
IAQ Outdoor — AI (4 to 20 mA)
T34-35
Condenser Fan — DO (115 vac)
T17-25
Remote Start/Stop — DI (24 vac)
T36-35
OFC2 — DO (115 vac)
T18-25
—
T37-38
Unloader 1 — DO (115 vac)
T19-25
—
T39-38
Unloader 2 — DO (115 vac)
T20-25
—
K1
Indoor Fan Relay — DO (LV)
T21-25
—
K2
Compr. 1 — DO (HV)
T22-25
Compressor 1 Safety — DI (24 vac)
K3
Compr. 2 — DO (HV)
TERMINAL NO.
ASSIGNMENT
TERMINAL NO.
ASSIGNMENT
T1-2
—
T23 and TB2-1
Fire — Evacuation — DI (24 vac)
T3-4
—
T24 and TB2-1
Fire — Smoke Purge — DI (24 vac)
T5-6
—
T26-27
—
T7-8
—
T28-29
—
T9-10
—
T30 and TB2-2
Alarm Light Indicator — DO (24 vac)
T11-12
—
T31
Power Exhaust Fire No. 1 — DO (115 vac)
T13-14
—
T33
Power Exhaust Fire No. 2 — DO (115 vac)
T15-16
—
T34
Power Exhaust Fire No. 3 — DO (115 vac)
T17 and TB2-1
Fan Status — DI (24 vac)
T36
Power Exhaust Fire No. 4 — DO (115 vac)
T18 and TB2-1
Filter Status - DI (24 vac)
T37
—
T19 and TB2-1
Field Applied Status — DI (24 vac)
T39
—
T20 and TB2-1
Demand Limit — DI (24 vac)
K1
—
T21 and TB2-1
Fire — Unit Shutdown — DI (24 vac)
K2
—
T22 and TB2-1
Fire — Pressurization — DI (24 vac)
K3
—
AI
—
Analog Input
OAT —
Outdoor-Air Temperature
AO
—
Analog Output
OFC —
Outdoor Fan Contactor
CCN —
Carrier Comfort Network
RAT —
Return-Air Temperature
CV
—
Constant Volume
SAT —
Supply-Air Temperature
DI
—
Direct Input
SPT —
Space Temperature
DO —
Direct Output
STO —
Space Temperature Offset
HV
—
High Voltage
T
—
Terminal
IAQ —
Indoor Air Quality
TB
—
Terminal Block
KV
—
Kilo-Ohms
VAV —
Variable Air Volume
LV
—
Low Voltage
Summary of Contents for WEATHERMAKER 48AJ020
Page 3: ...3 Fig 1 Roof Curb 48AJ AK020 030 and 48EJ EK024 034 Units ...
Page 4: ...4 Fig 2 Roof Curb 48AJ AK034 050 and 48EJ EK038 048 Units ...
Page 5: ...5 Fig 3 Roof Curb 48AJ AK060 and 48EJ EK054 068 Units ...
Page 97: ...97 Fig 78 Typical 48EK VAV 24 V Control Circuit ...
Page 99: ...99 Fig 80 Typical 48EK VAV 115 V Control Circuit ...
Page 100: ...100 Fig 81 Typical 48EJ CV 115 V Control Circuit ...
Page 101: ...101 Fig 82 Label Diagram Staged Gas Heat 48AJ AK AW AY020 050 and 48EJ EK EW EY024 048 Units ...
Page 102: ...102 Fig 83 Label Diagram Staged Gas Heat 48AJ AK AW AY060 and 48EJ EK EW EY054 068 Units ...