The alarm codes for the IGC control board are shown in
Table 44.
Table 44 — IGC Control Board LED Alarms
Diagnostic LEDs —
There are 3 LEDs (red, yellow, and
green) on the lower right hand side of the control board. The
red light is used to check unit operation and alarms. A constant
pulse is normal unit operation. A series of quick blinks indi-
cates an alarm. Refer to Table 45 below for a description of
alarms. The yellow LED blinks during transmission with the
CCN (Carrier Comfort Network). The green LED blinks dur-
ing transmission with the expansion board.
Table 45 — Control Board LED Alarms
LEGEND
INDICATION
ERROR MODE
ON
Normal Operation
OFF
Hardware Failure
1 FLASH
Fan ON/OFF Delay Modified
2 FLASHES
Limit Switch Fault
3 FLASHES
Flame Sense Fault
4 FLASHES
4 Consecutive Limit Switch Faults
5 FLASHES
Ignition Lockout Fault
6 FLASHES
Induced Draft Motor Fault
7 FLASHES
Rollout Switch Fault
8 FLASHES
Internal Control Fault
9 FLASHES
Software Lockout
LED
BLINKS
ERROR
CODE
DESCRIPTION
RESET
METHOD
ACTION TAKEN
BY CONTROL
TROUBLESHOOTING COMMENTS
1
—
Normal Operation
—
None
The expansion board and control board flash the red LED
in one-second intervals when the board is operating properly.
2
HF-13
Compressor 1 Safety
Automatic
and
Manual
Cooling disabled.
Automatic reset after
15 minutes. Manual if
repeated 3 times in
90 minutes.
The high or low pressure safety switch for compressor no. 1
has opened for 3 seconds. The error will be cleared and
compressor no. 1 will be allowed to turn on in 15 minutes.
If the safeties have been tripped 3 times in 90 minutes,
compressor no. 1 will be locked out until the control
board has been manually reset.
3
HF-14
Compressor 2 Safety
Automatic
and
Manual
Cooling disabled.
Automatic reset after
15 minutes. Manual if
repeated 3 times in
90 minutes.
The high or low pressure safety switch for compressor no. 2
has opened for 3 seconds. The error will be cleared and
compressor no. 2 will be allowed to turn on in 15 minutes.
If the safeties have been tripped 3 times in 90 minutes,
compressor no. 2 will be locked out until the control
board has been manually reset.
4
HF-15
Thermostat Failure
Automatic Alarm generated.
The thermostat is calling for both heating and cooling
at the same time. The unit will operate on a first call basis
and will automatically reset.
5
HF-05
SAT Thermistor Failure
Automatic Heating, cooling, and
economizer disabled.
The supply-air temperature (SAT) sensor has failed.
First check for wiring errors, then replace sensor.
6
HF-06
OAT Thermistor Failure
Automatic NTFC, IAQ purge,
economizer, and low
ambient DX cooling
locked out disabled.
The outside air temperature (OAT) sensor has failed.
First check for wiring errors, then replace sensor.
7
HF-03
Space Temp. Sen. Failure Automatic Disables unoccupied
cooling/heating, CV
economizer, and CV
cooling/heating.
The space temperature sensor has failed.
First check for wiring errors, then replace sensor.
8
HF-12
RAT Thermistor Failure
Automatic VAV heating
disabled.
The return-air temperature (RAT) sensor has failed.
Ensure that the unit is a VAV unit. If NOT a VAV unit set
DIP switch position 1 to the closed position and reset power.
Then check for wiring errors. Finally, replace sensor.
9
SE-05
Loss of Communications
with Expansion Board
Automatic Algorithms in
expansion board are
bypassed.
Communications between the expansion board and the
control board have been interrupted. Ensure that an
expansion board is installed and wired using the
wire harness supplied with the expansion module. If an
expansion board is not used ensure that DIP switch position
3 is in the closed position, and reset power.
10
HF-16
Control Board Failure
None
Control uses default
values. (May seem
as normal operation)
Generated when hardware has failed on control board.
Replace the control board.
Analog to Digital
Conversion
None
All outputs turned off.
11
HF-17
Expansion Board Failure
None
All outputs turned off. Generated when hardware has failed on the
expansion board. Replace the expansion board.
12
SE-23
Cooling SAT Low
Limit Shutdown
Automatic Alarm generated.
CV operation. When SAT low limits are below range and
compressor shut off.
DIP
—
Dual In-Line Package
VAV —
Variable Air Volume
Summary of Contents for WEATHERMAKER 48AJ020
Page 3: ...3 Fig 1 Roof Curb 48AJ AK020 030 and 48EJ EK024 034 Units ...
Page 4: ...4 Fig 2 Roof Curb 48AJ AK034 050 and 48EJ EK038 048 Units ...
Page 5: ...5 Fig 3 Roof Curb 48AJ AK060 and 48EJ EK054 068 Units ...
Page 97: ...97 Fig 78 Typical 48EK VAV 24 V Control Circuit ...
Page 99: ...99 Fig 80 Typical 48EK VAV 115 V Control Circuit ...
Page 100: ...100 Fig 81 Typical 48EJ CV 115 V Control Circuit ...
Page 101: ...101 Fig 82 Label Diagram Staged Gas Heat 48AJ AK AW AY020 050 and 48EJ EK EW EY024 048 Units ...
Page 102: ...102 Fig 83 Label Diagram Staged Gas Heat 48AJ AK AW AY060 and 48EJ EK EW EY054 068 Units ...