223
CONTROLS SETPOINT AND CONFIGURATION LOG
MODEL NUMBER:
Software Version
SERIAL NUMBER:
MBB
CESR131343--
DATE:
RCB
CESR131249--
TECHNICIAN:
ECB
CESR131465-
NAVI
CESR131227--
SCB
CESR131226--
CEM
CESR131174--
MARQ
CESR131171--
ITEM
EXPANSION
RANGE
DEFAULT
ENTRY
UNIT
UNIT CONFIGURATION
C.TYP
Machine Control Type
1 to 6 (multi-text strings)
4
CV.FN
Fan Mode (0=Auto, 1=Cont)
0 to 1 (multi-text strings)
1
RM.CF
Remote Switch Config
0 to 3 (multi-text strings)
0
CEM
CEM Module Installed
Yes/No
No
TCS.C
Temp.Cmp.Strt.Cool Factr
0 to 60 min
0
TCS.H
Temp.Cmp.Strt.Heat Factr
0 to 60 min
0
SFS.S
Fan Fail Shuts Down Unit
Yes/No
No
SFS.M
Fan Stat Monitoring Type
0 to 2 (multi-text strings)
0
VAV.S
VAV Unocc.Fan Retry Time
0 to 720 min
50
SIZE
Unit Size (20-60)
20 to 60
20
DP.XR
Disch.Press. Transducers
Yes/No
No
SP.XR
Suct. Pres. Trans. Type
0 to 1 (multi-text strings)
0
RFG.T
Refrig: 0=R22 1=R410A
0 to 1 (multi-text strings)
1
CND.T
Cnd HX Typ:0=RTPF 1=MCHX
0 to 1 (multi-text strings)
0
MAT.S
MAT Calc Config
0 to 2 (multi-text strings)
1
MAT.R
Reset MAT Table Entries?
Yes/No
No
MAT.D
MAT Outside Air Default
0 to 100%
20
ALTI
Altitude……..in feet:
0 to 60000
0
DLAY
Startup Delay Time
0 to 900 sec
0
STAT
TSTAT_Both Heat and Cool
Yes/No
No
AUX.R
Auxiliary Relay Config
0 to 3
0
SENS
INPUT SENSOR CONFIG
SPT.S
Space Temp Sensor
Enable/Disable
Disable
SP.O.S
Space Temp Offset Sensor
Enable/Disable
Disable
SP.O.R
Space Temp Offset Range
1 to 10
5
RRH.S
Return Air RH Sensor
Enable/Disable
Disable
FLT.S
Filter Stat.Sw.Enabled ?
Enable/Disable
Disable
COOL
COOLING CONFIGURATION
Z.GN
Capacity Threshold Adjst
–10 to 10
1
MC.LO
Compressor Lockout Temp
–20 to 55 dF
40
C.FOD
Fan-off Delay, Mech Cool
0 to 600 sec
60
MLV
Min. Load Valve? (HGBP)
Yes/No
No
DS.EN
Enable Digital Scroll?
Yes/No
No
DS.MC
DS Min Digital Capacity
25 to 100%
50
DS.AP
Dig Scroll Adjust Delta
0 to 100%
100
DS.AD
Dig Scroll Adjust Delay
15 to 60 sec
20
DS.RP
Dig Scroll Reduce Delta
0 to 100%
6
DS.RD
Dig Scroll Reduce Delay
15 to 60 sec
30
DS.RO
Dig Scroll Reduction OAT
70 to 120 dF
95
DS.MO
Dig Scroll Max Only OAT
70 to 120 dF
105
HPSP
Head Pressure Setpoint
80 to 150 dF
100
LASP
Low Ambient Setpoint
70 to 150
100
M.M.
Motor Master Control?
Yes/No
No
MM.OF
Motor Master Setpoint Offset
–20 to 20
–10
MM.RR
Motor Master PD Run Rate
10 to 120
10
MM.PG
Motor Master Proportional Gain
0.0 to 5
1
MM.DG
Motor Master Derivative Gain
0 to 5
0.3
MM.TI
Motor Master Integration Time
0 to 50
30
Summary of Contents for WEATHERMAKER 48A2020
Page 112: ...112 Fig 20 Typical Main Control Box Wiring Schematic 48 50A Units ...
Page 113: ...113 Fig 21 Typical Auxiliary Control Box Wiring Schematic ...
Page 114: ...114 Fig 22 Typical 2 Stage Gas Heat Wiring Schematic Size 060 Units Shown ...
Page 115: ...115 Fig 23 Typical Staged Gas Heat Wiring Schematic Size 060 Units Shown TO NEXT PAGE ...
Page 116: ...116 Fig 23 Typical Staged Gas Heat Wiring Schematic Size 060 Units Shown cont ...
Page 117: ...117 Fig 24 Typical Electric Heat Control Schematic 50 Series Size 060 Units Shown ...
Page 118: ...118 Fig 25 Typical Controls Option Wiring Schematic SW1 SW2 OR DEHUMIDIFY SWITCH ...
Page 119: ...119 Fig 26 Typical Power Schematic 48 50A2 A3 A4 A5 060 Unit Shown ...
Page 120: ...120 Fig 27 Typical Power Schematic of Greenspeed Low Ambient Option 48 50A 060 Unit Shown ...
Page 121: ...121 Fig 28 Typical Small Chassis Component Location Size 020 035 Units ...
Page 122: ...122 Fig 29 Typical Large Chassis Component Locations Size 040 060 Units ...
Page 185: ...185 APPENDIX C VFD INFORMATION cont Fig F Internal Enclosure Fan Replacement A48 7716 ...