211
APPENDIX G — OPTIONAL GREENSPEED/LOW AMBIENT CONTROL (cont)
Table Q — ACS320 VFD Greenspeed Parameters Tables, Part 2
LOOKUP VARIABLE
ABB ACS320 VFD
PARAMETER ID :
48EJ000340-DATA
48EJ000339-DATA
48EJ000330-DATA
48EJ000358-DATA
48EJ000380-DATA
48EJ000377-DATA
PKG
48EJ000340
48EJ000339
48EJ000330
48EJ000358
48EJ000380
48EJ000377
Motor Part Number
00PG000007210A
HD52AR381
HD52AR465
HD52AR465
00PG000007208A
HD52AR465
VFD Part Number
HK30WA534
HK30WA536
HK30WA534
HK30WA534
HK30WA534
HK30WA532
Drive HP
5
15
5
5
5
7.5
Number of Motors
2
3
2
2
2
3
LANGUAGE
9901
English (0)
English (0)
English (0)
English (0)
English (0)
English (0)
APPLIC MACRO
9902
HVAC (1)
HVAC (1)
HVAC (1)
HVAC (1)
HVAC (1)
HVAC (1)
MOTOR CTRL MODE
9904
SCALAR: FREQ
SCALAR: FREQ
SCALAR: FREQ
SCALAR: FREQ
SCALAR: FREQ
SCALAR: FREQ
VOLTAGE
9905
380
380
460
460
460
460
N. AMPS
9906
7.4
11.7
5.8
5.8
5.8
8.7
MOTOR NOM FREQ
9907
60Hz
60Hz
60Hz
60Hz
60Hz
60Hz
N. RPM
9908
850
850
850
850
850
850
N. HP
9909
5
7.5
5
5
5
7.5
EXT1 COMMANDS
1001
DI1 (1)
DI1 (1)
DI1 (1)
DI1 (1)
DI1 (1)
DI1 (1)
DIRECTION
1003
Forward (1)
Forward (1)
Forward (1)
Forward (1)
Forward (1)
Forward (1)
REF1 SELECT
1103
COMM (8)
COMM (8)
COMM (8)
COMM (8)
COMM (8)
COMM (8)
CONST SPEED SEL
1201
NOT SEL
NOT SEL
NOT SEL
NOT SEL
NOT SEL
NOT SEL
CONST SPEED 7
1208
0 Hz
0 Hz
0 Hz
0 Hz
0 Hz
0 Hz
RELAY OUT 1
1401
Ready (1)
Ready (1)
Ready (1)
Ready (1)
Ready (1)
Ready (1)
RELAY OUTPUT2
1402
Run (2)
Run (2)
Run (2)
Run (2)
Run (2)
Run (2)
RELAY OUT 3
1403
FAULT (-1)
FAULT (-1)
FAULT (-1)
FAULT (-1)
FAULT (-1)
FAULT (-1)
RUN ENABLE
1601
0
0
0
0
0
0
START ENABLE 1
1608
DI4 (4)
DI4 (4)
DI4 (4)
DI4 (4)
DI4 (4)
DI4 (4)
Parameter View
1611
3
3
3
3
3
3
MAX AMPS
2003
13.0
20.5
10.2
10.2
10.2
15.2
MIN FREQ
2007
0Hz
0Hz
0Hz
0Hz
0Hz
0Hz
MAX FREQ
2008
60Hz
60Hz
60Hz
60Hz
60Hz
60Hz
SWITCH FREQ
2606
4kHz
4kHz
4kHz
4kHz
4kHz
4kHz
START FCN
2101
Auto
Auto
Auto
Auto
Auto
Auto
STOP FCN
2102
(1) Coast
(1) Coast
(1) Coast
(1) Coast
(1) Coast
(1) Coast
ACCEL/DECEL
2201
Not Sel
Not Sel
Not Sel
Not Sel
Not Sel
Not Sel
ACCEL
2202
30s
30s
30s
30s
30s
30s
DECEL
2203
30s
30s
30s
30s
30s
30s
IR COMP VOLT
2603
0
0
0
0
0
0
COMM FAULT FUNC
3018
Last SP (3)
Last SP (3)
Last SP (3)
Last SP (3)
Last SP (3)
Last SP (3)
COMM FAULT TIME
3019
10 s
10 s
10 s
10 s
10 s
10 s
COMM PROT SEL
9802
LEN(6)
LEN(6)
LEN(6)
LEN(6)
LEN(6)
LEN(6)
TRIAL TIME
3102
300.0s
300.0s
300.0s
300.0s
300.0s
300.0s
DELAY TIME
3103
6.0s
6.0s
6.0s
6.0s
6.0s
6.0s
AR OVERCURRENT
3104
(1) Enable
(1) Enable
(1) Enable
(1) Enable
(1) Enable
(1) Enable
EFB PROTOCOL ID
5301
0601 hex
0601 hex
0601 hex
0601 hex
0601 hex
0601 hex
EFB STATION ID
5302
43/44
43/44
43/44
43/44
43/44
43/44
EFB BAUD RATE
5303
38.4 kb/s
38.4 kb/s
38.4 kb/s
38.4 kb/s
38.4 kb/s
38.4 kb/s
EFB PARITY
5304
8 NONE 1
8 NONE 1
8 NONE 1
8 NONE 1
8 NONE 1
8 NONE 1
EFB CTRL PROFILE
5305
DCU PROFILE
DCU PROFILE
DCU PROFILE
DCU PROFILE
DCU PROFILE
DCU PROFILE
Summary of Contents for WEATHERMAKER 48A2020
Page 112: ...112 Fig 20 Typical Main Control Box Wiring Schematic 48 50A Units ...
Page 113: ...113 Fig 21 Typical Auxiliary Control Box Wiring Schematic ...
Page 114: ...114 Fig 22 Typical 2 Stage Gas Heat Wiring Schematic Size 060 Units Shown ...
Page 115: ...115 Fig 23 Typical Staged Gas Heat Wiring Schematic Size 060 Units Shown TO NEXT PAGE ...
Page 116: ...116 Fig 23 Typical Staged Gas Heat Wiring Schematic Size 060 Units Shown cont ...
Page 117: ...117 Fig 24 Typical Electric Heat Control Schematic 50 Series Size 060 Units Shown ...
Page 118: ...118 Fig 25 Typical Controls Option Wiring Schematic SW1 SW2 OR DEHUMIDIFY SWITCH ...
Page 119: ...119 Fig 26 Typical Power Schematic 48 50A2 A3 A4 A5 060 Unit Shown ...
Page 120: ...120 Fig 27 Typical Power Schematic of Greenspeed Low Ambient Option 48 50A 060 Unit Shown ...
Page 121: ...121 Fig 28 Typical Small Chassis Component Location Size 020 035 Units ...
Page 122: ...122 Fig 29 Typical Large Chassis Component Locations Size 040 060 Units ...
Page 185: ...185 APPENDIX C VFD INFORMATION cont Fig F Internal Enclosure Fan Replacement A48 7716 ...