160
APPENDIX A — LOCAL DISPLAY TABLES (cont)
MODE — TIME CLOCK
MODE — OPERATING MODES
MODE — ALARMS
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
DEFAULT
PAGE NO.
TIME
TIME OF DAY
HH.MM
Hour and Minute
00:00
TIME
DATE
MONTH,DATE,DAY AND YEAR
MNTH
Month of Year
multi-text strings
MOY
DOM
Day of Month
0 to 31
DOM
DAY
Day of Week
multi-text strings
DOWDISP
YEAR
Year
e.g. 2003
YOCDISP
SCH.L
LOCAL TIME SCHEDULE
PER.1
PERIOD 1
DAYS
DAY FLAGS FOR PERIOD 1
Period 1 only
MON
Monday in Period
YES/NO
PER1MON
Yes
TUE
Tuesday in Period
YES/NO
PER1TUE
Yes
WED
Wednesday in Period
YES/NO
PER1WED
Yes
THU
Thursday in Period
YES/NO
PER1THU
Yes
FRI
Friday in Period
YES/NO
PER1FRI
Yes
SAT
Saturday in Period
YES/NO
PER1SAT
Yes
SUN
Sunday in Period
YES/NO
PER1SUN
Yes
HOL
Holiday in Period
YES/NO
PER1HOL
Yes
OCC
Occupied from
00:00
PER1_OCC
00:00
UNC
Occupied to
00:00
PER1_UNC
24:00
Repeated for periods 2-8………..
HOL.L
LOCAL HOLIDAY SCHEDULES
HD.01
HOLIDAY SCHEDULE 01
MON
Holiday Start Month
0 to 12
HOL_MON1
DAY
Start Day
0 to 31
HOL_DAY1
LEN
Duration (Days)
0 to 99
HOL_LEN1
Repeated for holidays 2-30……..
DAY.S
DAYLIGHT SAVINGS TIME
DS.ST
DAYLIGHT SAVINGS START
ST.MN
Month
1 to 12
STARTM
4
ST.WK
Week
1 to 5
STARTW
1
ST.DY
Day
1 to 7
STARTD
7
MIN.A
Minutes to Add
0 to 90
MINADD
60
DS.SP
DAYLIGHTS SAVINGS STOP
SP.MN
Month
1 to 12
STOPM
10
SP.WK
Week
1 to 5
STOPW
5
SP.DY
Day
1 to 7
STOPD
7
MIN.S
Minutes to Subtract
0 to 90
MINSUB
60
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
SYS.M
ascii string spelling out the system mode
string
HVAC
ascii string spelling out the hvac modes
string
CTRL
ascii string spelling out the “control type”
string
MODE
MODES CONTROLLING UNIT
OCC
Currently Occupied
ON/OFF
MODEOCCP
T.OVR
Timed Override in Effect
ON/OFF
MODETOVR
DCV
DCV Resetting Min Pos
ON/OFF
MODEADCV
SA.R
Supply Air Reset
ON/OFF
MODESARS
DMD.L
Demand Limit in Effect
ON/OFF
MODEDMLT
T.C.ST
Temp.Compensated Start
ON/OFF
MODETCST
IAQ.P
IAQ Pre-Occ Purge Active
ON/OFF
MODEIQPG
LINK
Linkage Active - CCN
ON/OFF
MODELINK
LOCK
Mech.Cooling Locked Out
ON/OFF
MODELOCK
H.NUM
HVAC Mode Numerical Form
0 to 24
MODEHVAC
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
WRITE STATUS
CURR
CURRENTLY ACTIVE ALARMS
this is a dynamic list of active alarms
strings
R.CUR
Reset All Current Alarms
YES/NO
ALRESET
ram config
HIST
ALARM HISTORY
this is a record of the last 20 alarms
strings
Summary of Contents for WEATHERMAKER 48A2020
Page 112: ...112 Fig 20 Typical Main Control Box Wiring Schematic 48 50A Units ...
Page 113: ...113 Fig 21 Typical Auxiliary Control Box Wiring Schematic ...
Page 114: ...114 Fig 22 Typical 2 Stage Gas Heat Wiring Schematic Size 060 Units Shown ...
Page 115: ...115 Fig 23 Typical Staged Gas Heat Wiring Schematic Size 060 Units Shown TO NEXT PAGE ...
Page 116: ...116 Fig 23 Typical Staged Gas Heat Wiring Schematic Size 060 Units Shown cont ...
Page 117: ...117 Fig 24 Typical Electric Heat Control Schematic 50 Series Size 060 Units Shown ...
Page 118: ...118 Fig 25 Typical Controls Option Wiring Schematic SW1 SW2 OR DEHUMIDIFY SWITCH ...
Page 119: ...119 Fig 26 Typical Power Schematic 48 50A2 A3 A4 A5 060 Unit Shown ...
Page 120: ...120 Fig 27 Typical Power Schematic of Greenspeed Low Ambient Option 48 50A 060 Unit Shown ...
Page 121: ...121 Fig 28 Typical Small Chassis Component Location Size 020 035 Units ...
Page 122: ...122 Fig 29 Typical Large Chassis Component Locations Size 040 060 Units ...
Page 185: ...185 APPENDIX C VFD INFORMATION cont Fig F Internal Enclosure Fan Replacement A48 7716 ...