c. Press
Dehumidifier
NOTE
: The DHUM on fan coil board is active in the open state. The ACC+
terminal for dehumidifiers is defaulted to active open. So, no other changes are
necessary. You can double check this setting on the thermostat
:
Menu > (hold) Service > Installation Settings > Equipment Setup >
Accessory > Dehum open
4) Complete the Guided Setup installation process
5) (Optional) Configure Cool to Dehumify
a. Select Menu > Profiles > Humidity Profiles > Dehumidification Setpoint
b. Default:
Disabled
c. Options:
Overcool temperature between 0.5oF and 5oF or disabled
Humidity setpoint between 46% and 58%
If Cool to Dehumidify is disabled, you will get the following operation
6) Congratulations, you have now set-up the system for dehumidification.