Installation Instructions

NOTE: 

Read  the  entire  instruction  manual  before  starting  the

installation.

Safety Considerations

Improper  installation,  adjustment,  alteration,  service,  maintenance,  or

use can cause explosion, fire, electrical shock, or other conditions which

may  cause  death,  personal  injury  or  property  damage.  Consult  a

qualified  installer,  service  agency  or  your  distributor  or  branch  for

information  or  assistance.  The  qualified  installer  or  agency  must  use

factory-authorized  kits  or  accessories  when  modifying  this  product.

Refer to the individual instructions packaged with the kits or accessories

when installing.
Follow  all  safety  codes. Wear  safety  glasses,  protective  clothing,  and

work gloves. Have a fire extinguisher available. Read these instructions

thoroughly and follow all warnings and cautions included in literature

and attached  to  the  unit. Consult local  building codes and  the current

edition  of  the  National  Electrical  Code  (NEC)  NFPA  70.  In  Canada,

refer to the current editions of the Canadian Electrical Code CSA C22.1.
Recognize safety information. When you see this symbol   on the unit

and  in  instructions  or  manuals,  be  alert  to  the  potential  for  personal

injury.  Understand  the  signal  words  DANGER,  WARNING,  and

CAUTION.  These  words  are  used  with  the  safety-alert  symbol.

DANGER identifies the most serious hazards, which will result in severe

personal  injury  or  death.  WARNING  signifies  hazards,  which  could

result in personal injury or death. CAUTION is used to identify unsafe

practices,  which  may  result  in  minor  personal  injury  or  product  and

property  damage.  NOTE  is  used  to  highlight  suggestions  which  will

result in enhanced installation, reliability, or operation.

Introductions

Smart Sensors are optional replacements for Remote Room Sensors used

with communicating Zoning systems (see equipment Product Data Sheet

for  compatibility  with  this  Smart  Sensor).  It  provides  a  temperature

display on a touch screen to adjust the desired temperature within the

zone. It also displays outdoor temperature and indoor humidity. When

used with a Communicating System Control - FAN, HOLD and HOLD

UNTIL features are available. 

Installation Considerations

Any zone may use a Smart Sensor. The Smart Sensor can be “home run”

wired directly to the Damper Control Module, or “daisy chained” from

the  wall  control  or  another  Smart  Sensor  via  4-wire  ABCD

communication  bus.  Ordinary  thermostat  wire  is  recommended;

however, solid conductor, stranded, or shielded wire may be used. Use

22  AWG  or  larger  for  normal  wiring  applications.  Continuous  wire

lengths over 100 ft. should use 20 AWG or larger. Plan the connection of

each Smart Sensor to provide easiest wiring route.

NOTE: 

Whenever possible, it is suggested to always “home run” wires

back to the Damper Control Module for convenience of troubleshooting.

Using a “pig-tailed” connection, or a field supplied terminal block may

be helpful in achieving proper wire termination at the Damper Control

Module.
A  Smart  Sensor  may  now  be  used  to  control  Zone  1.  In  addition,  a

Remote Room Sensor may also be used in the same zone. If a Remote

Room Sensor is applied in the same zone, the Remote Room Sensor has

temperature priority over the Smart Sensor.

A200265

Fig. 1 – Smart Sensor SYSTXZNSMS01

Installation

Step 1 – Select Smart Sensor Location 

Sensor should be mounted: 

• Approximately 5 ft. (1.5m) from floor. 

• Close to center of zone, preferably on inside partitioning wall.

• On section of wall without pipes or ductwork.

• Where wiring can be routed to it within wall. Avoid running directly

next to other AC power.

Sensor should NOT be mounted: 

• Close to a window, on outside wall, or next to a door leading to the

outside.

• Exposed to direct light and heat from a lamp, sun, fireplace, or other

temperature radiating object which may cause a false reading. 

• Close  to  or  in  direct  airflow  from  supply  registers  and  return-air

grilles. 

• In  areas  with  poor  air  circulation,  such  as  behind  a  door  or  in  an

alcove. 

• Do not run wires next to AC power lines.

Step 2 – Install Smart Sensor 

1. Turn OFF all power to unit.
2. If an existing thermostat or sensor is being replaced: 

a. Remove existing device from wall.

b.  Disconnect wires from existing device, 1 at a time. Be careful 

not to allow wires to fall back into wall.

c. Discard or recycle old device.

d. If 4 wires exist in wall, they may be used. If not, plan and route 

wiring to connect with either the Damper Control Module, or 

User Interface. Multiple Smart Sensors may be daisy chained 

together, but somewhere chain must connect to either Damper 

SYSTXZNSMS01

Smart Sensor for Zoning

WARNING

!

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

Before installing sensor, turn off all power to unit. There may be more

than 1 power disconnect.

Summary of Contents for SYSTXZNSMS01

Page 1: ...l Module or daisy chained from the wall control or another Smart Sensor via 4 wire ABCD communication bus Ordinary thermostat wire is recommended however solid conductor stranded or shielded wire may be used Use 22 AWG or larger for normal wiring applications Continuous wire lengths over 100 ft should use 20 AWG or larger Plan the connection of each Smart Sensor to provide easiest wiring route NOT...

Page 2: ...hrough the fan modes of AUTO or OFF LOW MED and HIGH AUTO model will operate the fan only when the system is heating or cooling that zone LOW MED and HIGH modes will run continuously at that speed until you switch the zone back to AUTO Fan Mode Changing Zone Address To change an existing zone address enter the setup menu by swiping from Left to Right on the Home Screen to display the Fan Screen pr...

Page 3: ...ses the up down buttons shall appear again and an override of the vacation setpoints will be allowed The middle of the screen shall display Vacation when active Error Display The middle of the screen shall display the following errors when they occur COM ERROR Communication Error will be displayed if the Smart Sensor cannot send or receive communication data with the Communicating System Control C...

Page 4: ...ime Mode Screen where the type of Override can be changed to HOLD permanent length of time OVERRIDE HOLD UNTIL specified time length SCHEDULED removes any override or UNOCCUPIED User Interface wall control only A200275 A200276 Temporary override time can be changed in 15 minute increments by pressing the OVERRIDE or HOLD UNTIL button to increase or decrease the override timer A200277 NOTE Override...

Reviews: